Installation Manual 25
ENGLISH
Wiring Connection
Wiring for the Humidity Regulator (Locally Procured)
<LZ-H***GXH series only>
1. Pass into the electric parts box together with the power wire through the power wiring through-hole.
2. Remove the short-circuit wires (3 and 4) on the TB 2 terminal block and connect the wiring for the
humidity regulator.
3. Secure with cramping material together with the power wire.
Wiring specifications
Sheathed wire (should be complied with IEC60245 standard)
Size 0.75 - 1.25 mm
2
Length MAX. 100 m
External contact specifications Normally closed contact (Current tolerance 10 mA - 0.5 A)
• If using humidistat, install one per ventilation unit.
Controlling more than one ventilation unit with a single humidity controller may prevent normal
humidity operation and cause water leakage, etc.
CAUTION