MASTER-K10S1
SEND [FUN(159)] : Transmission data from master to slave
RECV [FUN(158)] : Receiving data from slave to master
Instruction Form :
St : Station number of slave PLC to communicate.(This of master PLC is always h1F.)
S1 : Beginning address of word memory device of master PLC in which data to be
transmitted to slave is stored.
D1 : Beginning address of word memory device of slave PLC in which data to be
received from master will be stored.
S2 : Beginning address of word memory device of slave PLC in which data to be
transmitted to master is stored.
D2 : Beginning address of word memory device of master PLC in which data to be
received from slave will be stored.
n : The number of word data to be transmitted or received.(Hex. or Decimal)
[ SEND St S1 D1 n ]
[ RECV St D2 S2 n ]
Instruction
Note
When the transmitted data from master PLC is stored to P area of slave directly,
the output data of P area of slave PLC may clear during operation mode of slave PLC
changing(PROGRAM mode RUN mode) according to PLC operation system.
The range of address(D1, S2) of word memory device for slave PLC in the SEND/RECV
can not be exceed that of master PLC.