LG Multi V 5 ARUV144DTE5 - Auto Dust Removal Mode; Mode Setting Method for Auto Dust Removal; Compressor Max. Frequency Limit; Mode Setting Method for Compressor Limit

LG Multi V 5 ARUV144DTE5
41 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
ENGLISH
Mode Setting
Setting
Operation
time
Operating
time
Repeat
cycle
Detail of function
op1
Stop
+2 hour
5 minutes 2hour
After product stopped 2 hour, fan operating 5
min(Repeated every 2 hours)
op2
stop
+5 minutes
3 minutes
Twice in
2 hour
after product stopped 5 minutes, fan
operating 3 min (Limited to two times within
2 hours)
op3
stop
+5 minutes
3 minutes 1 time
after product stopped 2 hour, fan operating 5
min(Repeated every 2 hours)
op4
Stop
+1 minutes
1 minutes 1 time
after product stopped 5 minutes, fan
operating 3 min(when io module
connection/one-time operation)
op5
Stop
+1 minutes
1 minutes
Low
speed
after product stopped 1 minutes, fan
operating 1 min(every time the product stops)
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn11” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”~“op5” Push the ‘’ button
Auto Dust Removal Mode is set
Function setting
Setting Inverter (Hz)
oFF -
op1 143 Hz
op2 135 Hz
op3 128 Hz
op4 120 Hz
op5 113 Hz
op6 105 Hz
op7 98 Hz
op8 90 Hz
op9 83 Hz
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn13” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”~“op7” Push the ‘’ button
ODU Fan Max. RPM Limit Mode is set
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn 12” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”,“op9” Push the ‘’ button
Cool & Heat Selection mode is set
ODU Fan Max. RPM Limit
Mode setting method
Compressor Max. Frequency Limit
Mode setting method
Auto Dust Removal Mode
The ability to set reverse run outdoor fan to remove dust, heat
exchanger.
Mode setting method
MAX. RPM Limit Setting
Chassis UXA UXB
Fan MAX. RPM
Limit (RPM)
oFF 880 1000
oP1 -20 -50
oP2 -40 -100
oP3 -60 -150
oP4 -80 -200
oP5 -100 -250
oP6 -120 -300
oP7 -140 -350
CAUTION
!