34
ENGLISH
SLC(Smare Lode Control) Mode
Master unit PCB DIP switch on : No.5
Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button
Select the Function using ‘▶’, ‘◀’ Button :
“Fn14” Push the ‘●’ button
Select the Option using ‘▶’, ‘◀’ Button :
“oFF”,“op1”~“op3” Push the ‘●’ button
SLC(Smare Lode Control) Mode is set
Setting Mode Detail of function
oFF Not Setting -
oP1 Smooth Mode Slowly control, a target pressure value
oP2 Normal Mode Normal control, a target pressure value
oP3 Peak Mode Fast control, a target pressure value
Master unit PCB DIP switch on : No.5
Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button
Select the Function using ‘▶’, ‘◀’ Button :
“Fn16” Push the ‘●’ button
Select the Option using ‘▶’, ‘◀’ Button :
“oFF”,“on” Push the ‘●’ button
Humidity Reference Control mode is set
Mode setting
- on:using humidity sensor
- oFF:not setting
<Using of humidity sensor>
- When used cooling operation of SLC function,it will improve energy
effcience because evaporation temperature wll be decreased
Master unit PCB DIP switch on : No.5
Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button
Select the Function using ‘▶’, ‘◀’ Button :
“Fn16” Push the ‘●’ button
Select the Option using ‘▶’, ‘◀’ Button :
“Fn19” Push the ‘●’ button
Select the Option using ‘▶’, ‘◀’ Button :
“on”,“oFF” Push the ‘●’ button
Central Control Connection at Indoor
Unit side Mode is set
Compressor Input Current Limit
Master unit PCB DIP switch on : No.5
Select the mode using ‘▶’, ‘◀’ Button :
“Func” Push the ‘●’ button
Select the Function using ‘▶’, ‘◀’ Button :
“Fn20” Push the ‘●’ button
Select the Option using ‘▶’, ‘◀’ Button :
“oFF”,“op1”~”op10” Push the ‘●’ button
Compressor Input Current Limit mode is set
Mode Compressor Input Current Limit
op1 95 %
op2 90 %
op3 85 %
op4 80 %
op5 75 %
op6 70 %
op7 65 %
op8 60 %
op9 55 %
op10 50 %
Compressor Input Current Limit
System Input Current Control
Mode setting method
Central Control Connection at Indoor Unit side
Mode setting method
Humidity Reference
Mode setting method
SLC (Smart Load Control)
Function for set the variable target pressure which for the high
efficiency and comport operation depend on ODU load.
Mode setting method
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, capacity may go down.
CAUTION
!