5. Wiring Diagrams
Ceiling Concealed Duct(Middle Static) _ 11
Indoor Units
   CONNECTOR NUMBER 
LOCATION POINT                       FUNCTION
  CN-POWER                      AC Power supply                     AC Power line input for indoor controller
  CN-MOTOR1                    Fan motor output                     Motor output of BLDC
  CN-MOTOR2                    Fan motor output                     Motor output of BLDC
  CN-D_PUMP                    Drain pump output                   AC output for drain pump 
  CN-COM                           Communication                       Connection between indoor and outdoor 
  CN-EEV                            EEV Output                             EEV Control output 
  CN-FLOAT                        Float switch input                     Float switch sensing 
  CN-PIPE_IN                      Suction pipe sensor                 Pipe in thermistor 
  CN-PIPE_OUT                  Discharge pipe sensor            Pipe out thermistor
  CN-ROOM                        Room sensor                           Room air thermistor 
  CN-REMO                         Remote controller                    Remote control line 
  CN-ZONE                         Zontroller                                 Zone control line  
  CN-DISPLAY                    RF Remote controller              RF Remote control line 
  CN-CC                              Dry contact                              Dry contact line 
   CN-EXT                               External On/Off                          External On/Off signal input
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
Function Description Setting Off Setting On
Default
SW1
Communication
N/A (Default) - - Off
SW2
Cycle
N/A (Default) - - Off
SW3
Group Control
Selection of Master or Slave
Master Slave Off
SW4
Dry Contact Mode
Selection of Dry Contact Mode
Wired/Wireless remote controller selec-
tion of Manual or Auto operation Mode
Auto Off
SW5
Installation
Fan continuous operation
Continuous operation Removal - Off
SW6
Heater linkage
N/A - - Off
SW7
Ventilator linkage
Selection of Ventilator linkage
Linkage Removal Working
Off
Vane selection (Console)
Selection of up/down side Vane
Up side + Down side Vane
Up side Vane Only
Region selection
Selection tropical region General model Tropical model
SW8
Etc.
Spare - - Off
M2 / M3 Chassis