14 _ Ceiling Cassette 4-way
Indoor Units
5. Wiring Diagrams
TM/TN/TP Chassis
       Dip Switch Setting                     Off                   On                                                  Remarks
      SW3                  GROUP                  Master                 Slave          Group Control setting using Wired Remote Controller
                                                                                                              Old Dry Contact Mode Setting
                                                                                                              1. Variable : Auto/Manual Mode can be chosen by Wide wired
      SW4            DRY CONTACT           Variable                Auto   remote controller or Wireless remote controller
(When shipped from Factory ’ Manual Mode)
                                                                                                              2. Auto : For Dry Contact, it is always Auto mode.
                                                                                                              1. Duct model
-. OFF : Default(not operate continuosly )
-. ON  : Fan operate continuosly 
      SW5                 EXTRA 1                    Off                      On             2. Cassette Model  : No Function
                                                                                                              3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON  : Floor
For Multi V models, Dip switch 1,2,6,7,8 must be set OFF
Those are used for the other model.
CONNECTOR NUMBER LOCATION POINT FUNCTION
            CN-MOTOR1                      Fan motor output                               Motor output of BLDC
             CN_DPUMP                       Drain pump output                             AC output for drain pump
              CN-GRILL                         Elevation grill                                     Elevation grill line
                CN-PTC                          Aux heater                                         Aux heater line
               CN-LEAK                         Refrigerant leak detector                   Refrigerant leak detector line
               CN-AIRC                          Air cleaner                                         Air cleaner line
            CN-DISPLAY                      Display                                               Display of indoor status
             CN-OPTION                       Option pwb.                                       Communication between main and option
                CN-EEV                          EEV Output                                       EEV Control output
              CN-FLOAT                        Float switch input                               Float switch sensing
              CN-ROOM                        Room sensor                                     Room air thermistor
             CN-PIPE_IN                       Suction pipe sensor                           Pipe in thermistor
           CN-PIPE_OUT                     Discharge pipe sensor                       Pipe out thermistor
              CN-REMO                        Remote controller                              Remote control line
                 CN-CC                           Dry contact                                        Dry contact line
              CN-COMM                        Communication                                 Communication between indoor and outdoor
              CN-VANE1                        Step motor                                         Step motor output
              CN-VANE2                        Step motor                                         Step motor output
                CN-485                           Communication                                  Connection between indoor and outdoor
                CN-EXT                          External On/Off                                  External On/Off signal input