EasyManua.ls Logo

LG MULTI V ARNU243TTD4 - Page 57

LG MULTI V ARNU243TTD4
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FOUR-WAY | 57
Four-Way Ceiling Cassette Product Data
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©
/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
Model No. ARNU243TPC4 ARNU283TPC4
&RROLQJ0RGH3HUIRUPDQFH
Capacity (Btu/h)
24,200 28,000
Power Input
1
(W)
33 33
+HDWLQJ0RGH3HUIRUPDQFH
Capacity (Btu/h)
27,300 31,500
Power Input
1
(W)
33 33
(QWHULQJ0L[HG$LU
Cooling Max (°F WB)
76 76
Heating Min (°F DB)
59 59
8QLW'DWD
Refrigerant Type
2
R410A R410A
Refrigerant Control
EEV EEV
Sound Pressure
3
dB(A) (H/M/L)
36 / 34 / 31 39 / 35 / 33
Net Unit Weight (lbs.)
48 48
Shipping Weight (lbs.)
58 58
Grill Weight (lbs)
13 13
Grill Shipping Weight (lbs)
20 20
Communication Cable
4
(No. x AWG)
2 x 18 2 x 18
)DQ
Type
Turbo Turbo
Quantity
11
Motor/Drive
Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM)
600 / 530 / 459 671 / 565 / 494
3LSLQJ
Liquid Line (in., O.D.)
3/8 Flare 3/8 Flare
Vapor Line (in., O.D.)
5/8 Flare 5/8 Flare
Condensate Line (in., I.D.)
11
Table 27: Four-Way Ceiling Cassette (3' x 3' TP Frames) Indoor Unit General Data.
FOUR-WAY CEILING CASSETTE
General Data
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national codes. See page
61 for detailed electrical data.
This unit comes with a dry nitrogen charge.
All capacities are net with a combination ratio between 95-105%.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice.
Current certified ratings are available at www.ahridirectory.org.
1
Power Input is rated at high speed.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy
R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608
of CAA.
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4
Communication cable between Master ODU to IDUs / HRUs to be 18 AWG, 2-conductor, twisted,
stranded, shielded. Ensure the communication cable shield is properly grounded to the Master ODU
chassis only.
Do not ground the ODU to IDUs / HRUs communication cable at any other point.
Wiring must comply with all applicable local and national codes.

Other manuals for LG MULTI V ARNU243TTD4

Related product manuals