FOUR-WAY CEILING CASSETTE
Electrical Data
Table 31: Four-Way Ceiling Cassette (2' x 2' and 3' x 3' Frames) Indoor Unit Electrical Data.
Model Voltage Range MCA MOP Rated Amps (A)
Power Supply Power Input (W)
Hz Volts Phase Cooling Heating
[)UDPHV
ARNU053TRD4
187-253
0.25
15
0.2
60 208-230 1
30 30
ARNU073TRD4 0.25 0.2 30 30
ARNU093TRD4
0.25 0.2 30 30
ARNU123TRD4 0.25 0.2 30 30
ARNU153TQD4 0.25 0.2 30 30
ARNU183TQD4 0.25 0.2 30 30
[)UDPHV73Ǝ+LJK
ARNU243TPC4
187-253
0.19
15
0.15
60 208-230 1
33 33
ARNU283TPC4 0.19 0.15 33 33
[)UDPHV71Ǝ+LJK
ARNU073TNA4
187-253
0.71
15
0.56
60 208-230 1
144 144
ARNU093TNA4 0.71 0.56 144 144
ARNU123TNA4 0.71 0.56 144 144
ARNU153TNA4 0.71 0.56 144 144
ARNU183TNA4 0.71 0.56 144 144
ARNU243TNA4 0.71 0.56 144 144
ARNU363TNC4 0.71 0.56 144 144
[)UDPHV70Ǝ+LJK
ARNU243TMA4
187-253
1.6
15
1.3
60 208-230 1
144 144
ARNU283TMA4 1.6 1.3 144 144
ARNU363TMA4 1.6 1.3 144 144
ARNU423TMC4
1.6 1.3 144 144
ARNU483TMC4 1.6 1.3 144 144
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of a fuse, use the circuit breaker.