FOUR-WAY CEILING CASSETTE
Electrical Wiring Diagram
TP, TN, and TM Frames
Table 34: TP, TN, and TM Frame Wiring Diagram Legend.
Table 35: TP, TNC, and TMC Frame DIP Switch Settings.
*For Gen 4 Multi V four-way ceiling cassette indoor units, DIP switches 1, 2, 5, 6, and 8 must be set to OFF. These DIP switch-
es are used for other models.
**To enable Generation 4 features, outdoor unit DIP switch no. 3 must be set to ON. Please refer to the Multi V 5, Multi V IV,
Multi V Water IV, Multi V S Engineering Manual for additional information.
3ODVPD¿OWHUNLWDFFHVVRULHVDUHDYDLODEOHVHSDUDWHO\$OZD\VIROORZDOOORFDOVWDWHDQGQDWLRQDOEXLOGLQJFRGHVZLWKWKHXVHRIWKLVRUDQ\SURGXFW
DIP Switch Setting Off On Remarks
SW3 GROUP CONTROL Master Slave
Group control setting using 7-Day Programmable Controller; selects Master /
Slave on each indoor unit
SW4
DRY CONTACT
MODE
Variable Auto
Sets operation mode for optional Dry Contact accessory
1. Variable: Auto or Manual Mode can be set through 7-Day
Programmable Controller or Wireless Remote Controller
(factory default setting is Auto if there is no setting)
2. Auto: For Dry Contact, it is always Auto mode
SW7
VENTILATOR
INTERLOCK
Off On
Selects ventilator interlock function for four-way ceiling cassette indoor units.
1. On: Automatic (vent relay will be turned on after ten [10] seconds
of indoor unit operation
2. Off: Manual (ventilator needs to be set through the controller)
Terminal Purpose Function
CN-MOTOR1
Fan motor output Motor output of BLDC
CN-D_PUMP
Drain pump output AC output for drain pump
CN-GRILL
Elevation grille Elevation grille connection
CN-PTC
Auxiliary heater Auxiliary heater connection
CN-FLOAT
Float switch input Float switch sensing
CN-EEV
EEV Output EEV control output
CN-DUST
N/A N/A
CN-DISPLAY
Display Display of indoor status
CN-OPTION
Optional PCB EEPROM Option PCB connection
CN-WF
Wi-Fi module Wi-Fi module connection
CN-ROOM
Room sensor Room air thermistor
CN-PIPE_IN
Suction pipe sensor Pipe in thermistor
CN_LEAK
Leak sensor Leak sensor connection
CN-PIPE_OUT
Discharge pipe sensor Pipe out thermistor
CN-EXT
External on/off controller External on/off controller connection
CN-HUMID
N/A N/A
CN-CC
Dry contact Dry Contact connection
CN-AIRC
Air cleaner* Air cleaner control*
CN-VANE2
Step motor Step motor output
CN-VANE1
Step motor Step motor output
CN-485
Communication Connection between indoor and outdoor units
CN-COM
Communication Connection on Sub PCB between indoor and outdoor units
CN-REMO
Wired remote controller Wired remote control connection
CN-POWER
AC Power supply AC Power line