STANDARD | 113
Standard Wall-Mounted
Due to our policy of continuous product innovation, some specications may change without notication.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 59: ARNU363SVA4 Heating Capacity Table.
STANDARD WALL-MOUNTED
Heating Capacity Tables
ARNU363SVA4
Model No. /
Capacity Index
Outdoor
Air Temp.
Indoor Air Temperature (°F DB)
59 61 64 67 70 73 76 80
°F DB °F WB
TC TC TC TC TC TC TC TC
MBh MBh MBh MBh MBh MBh MBh MBh
ARNU363SVA4 /
36.2
-21.6 -22.0 18.8 18.8 18.8 18.8 18.5 18.5 18.5 18.5
-17.1 -17.5 21.0 21.0 21.0 21.0 20.7 20.7 20.7 20.7
-12.6 -13 23.3 23.3 23.3 23.3 23.0 23.0 23.0 23.0
-7 -7.6 24.1 24.1 24.1 24.1 23.7 23.7 23.7 23.7
-4 -4.4 24.8 24.8 24.8 24.8 24.4 24.4 24.4 24.4
0 -0.4 25.5 25.5 25.5 25.5 25.5 25.2 25.2 25.2
5 4.5 28.9 28.5 28.1 28.1 28.1 28.1 28.1 28.1
10 9 30.0 30.0 30.0 29.6 29.6 29.6 29.6 29.6
15 14 31.8 31.8 31.8 31.8 31.8 31.8 31.5 31.1
20 19 33.7 33.7 33.7 33.7 32.9 32.9 32.4 32.0
25 23 35.2 35.2 35.2 35.2 35.2 34.4 34.0 32.4
30 28 35.9 35.9 35.9 35.9 35.9 35.2 34.0 32.4
35 32 37.0 37.0 37.0 37.0 36.6 35.9 34.0 32.4
40 36 38.5 38.5 38.5 38.5 37.0 35.9 34.0 32.4
45 41 40.0 40.0 40.0 38.9 37.0 35.9 34.0 32.4
47 43 41.4 41.1 40.7 38.9 37.0 35.9 34.0 32.4
50 46 44.4 42.6 40.7 38.9 37.0 35.9 34.0 32.4
55 51 45.3 42.9 40.7 38.9 37.0 35.9 34.0 32.4
60 56 45.3 42.9 40.7 38.9 37.0 35.9 34.0 32.4
Low ambient performance with LGRED° heat technology is included in Multi V 5 Air Source Units produced after February 2019.
TC: Total Capacity (MBh).
The System Combination Ratio must be between 50–130%.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice.
Current certified ratings are available at www.ahridirectory.org.
For outdoor unit performance data, see the respective outdoor unit performance data
manuals on https://lghvac.com/commercial.