ART COOL MIRROR
Mechanical Specications
Casing
Units are designed to mount on a vertical surface and come com-
plete with an installation mounting guide and a separate hanging 
bracket. The unit case is manufactured with coated metal. Cold 
surfaces are covered with a coated polystyrene insulating material.
Finish
The unit case has a light gray / silver matte finish. The front surface 
of the unit has an architectural flat panel smoked mirror finish. 
Fan Assembly and Control
The unit has a single, direct-drive, crossflow tangential Sirocco fan 
made of high strength ABS BSN-7530 polymeric resin. The fan motor 
is a Brushless Digitally Controlled (BLDC) design with permanently 
lubricated and sealed ball bearings. The fan motor includes thermal, 
overcurrent and low RPM protection. The fan / motor assembly is 
mounted on vibration attenuating rubber grommets. The fan impeller 
is statically and dynamically balanced. The fan speed is controlled 
using a microprocessor-based direct digital control algorithm that 
provides a high fan speed in cooling thermal ON and low fan speed 
in cooling thermal OFF, high fan speed in heating thermal ON and 
fan off in heating thermal OFF. The fan speeds can be field adjusted 
between low, medium, and high speeds. The fan speed algorithm 
provides a field-selectable fixed-speed or auto-speed setting that 
changes the fan speed to simulate natural airflow.
Air Filter
Return air is filtered with a removable, washable filter with anti-fun-
gal treatment. Filter access is from the front of the unit without the 
use of tools.
Airflow Guide Vanes
5–15 MBh
The indoor unit is provided with a motorized oscillating guide vane 
that automatically changes the direction of up-and-down airflow. 
The indoor unit includes factory installed, manually adjustable guide 
vanes that control the side-to-side direction of supplied airflow.
18-24 MBh
The indoor unit is provided with a motorized sweeping guide vane 
that automatically changes the direction of airflow from side-to-side 
and up-and-down.
 
Microprocessor Control
The unit is provided with an integrated microprocessor controller  
capable of performing functions necessary to operate the system 
without the use of a wall-mounted controller. A temperature  
thermistor is factory mounted in the return air stream. All unit 
operation parameters, excluding the operating schedule, are 
stored in non-volatile memory resident on the unit microprocessor. 
Operating schedules are stored in select models of the optional, 
wall-mounted, local or central controllers. The field-supplied commu-
nication cable between the indoor unit(s) and outdoor unit is to be 
a minimum of 18 AWG, 2 conductor, stranded, and shielded cable 
(RS-485), terminated via screw terminals on the control boards. 
The microprocessor control provides the following functions: auto 
addressing, self-diagnostics, auto restart following power restoration, 
test run, and will operate the indoor unit using one of five operation 
modes:
1.  Auto Changeover (Heat Recovery only)
2.  Heating
3.  Cooling
4.  Dry
5.  Fan Only
For Heat Recovery systems the Auto Changeover setting automati-
cally switches control of the indoor unit between Cooling and Heating 
modes based on space temperature conditions.
For Heat Pump systems, heated or cooled air delivery is dependent 
upon outdoor unit operating mode. In Heating mode, the micropro-
cessor control will activate indoor unit operation when the indoor 
room temperature falls below set-point temperature. At which point, 
a signal is sent to the outdoor unit to begin the heating cycle. The in-
door unit fan operation is delayed until coil pipe temperature reaches 
76°F. Significant airflow is generated when pipe temperature reaches 
80°F. A field-selectable option maintains fan operation for 30 minutes 
following cooling cycle operations. The unit is equipped with an in-
frared receiver designed to communicate with an LG wireless remote 
controller. In lieu of wireless remote or factory return air thermistor, 
screw terminals on the microprocessor circuit board accommodate 
various models of wall-mounted local controllers. The unit micropro-
cessor is capable of accepting space temperature readings concur-
rently or individually from either:
1.  Wall-mounted wired controller(s)
2.  Factory-mounted return air thermistor
A single indoor unit has the capability of being controlled by up to 
two local wired controllers. The microprocessor controls space tem-
perature using the value provided by the temperature sensor sensing 
a space temperature that is farthest away from the temperature 
set-point. The microprocessor control provides a cooling or heating 
mode test cycle that operates the unit for 18 minutes without regard 
to the space temperature. If the system is provided with an optional