EasyManua.ls Logo

LG Multi V Art Cool ARNU093SFA4 - Page 28

LG Multi V Art Cool ARNU093SFA4
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28 | ART COOL
TM
MULTI V Wall-Mounted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Electrical Data
Model Number
Voltage
Range
MCA MOP
Rated
Amps (A)
Power Supply Power Input (W)
Hz Volts Phase
Max.
Cooling
Max.
Heating
H / M/ L at
Factory Default
SJ Frames
ARNU053SJR4
187-253
0.31
15
0.25
60 208-230V 1
30 30
11 / 10 / 9
ARNU073SJR4 0.31 0.25 30 30 12 / 11 / 9
ARNU093SJR4 0.31 0.25 30 30 13 / 12 / 9
ARNU123SJR4 0.31 0.25 30 30 15 / 13 / 11
ARNU153SJR4 0.31 0.25 30 30
23 / 18 / 11
SK Frames
ARNU183SKR4
187-253
0.65
15
0.52
60 208-230V 1
53 53 32 / 26 / 16
ARNU243SKR4 0.65 0.52 53 53 39 / 26 / 16
Table 13: Art Cool Mirror Wall-Mounted Indoor Unit Electrical Data.
ART COOL MIRROR
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use the circuit breaker.
Max. power input is rated at maximum setting value.

Related product manuals