98 | STANDARD
MULTI V Wall-Mounted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 44: ARNU093SJA4 Cooling Capacity Table.
Model No. /
Capacity Index
Outdoor
Air
Temp.
(°F DB)
Indoor Air Temperature (°F DB / WB)
68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
ARNU093SJA4 /
9.6
-9.9 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
-5 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
0 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
5 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
10 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
14 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
20 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
23 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
25 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
30 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
35 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
40 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
45 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
50 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
55 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.4 7.7
60 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.3 7.7
65 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 12.1 7.6
70 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 11.9 7.4
75 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.4 7.7 11.6 7.3
80 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.8 7.8 11.1 7.7 11.3 7.2
85 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.6 7.7 10.8 7.4 11.0 6.9
90 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.5 7.6 10.6 7.2 10.8 6.9
95 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.3 7.6 10.5 7.2 10.6 6.8
100 6.3 5.6 7.7 6.4 8.6 6.8 9.6 7.3 10.1 7.4 10.3 7.1 10.5 6.7
105 6.3 5.6 7.3 6.1 8.2 6.5 9.2 6.9 9.6 6.9 9.9 6.9 10.2 6.6
110 6.2 5.4 6.9 5.8 7.7 6.1 8.6 6.5 9.0 6.5 9.4 6.5 9.8 6.4
115 6.0 5.2 6.6 5.5 7.2 5.7 8.1 6.2 8.5 6.2 8.9 6.2 9.4 6.1
118 5.9 5.1 6.2 5.2 6.9 5.4 7.8 5.9 8.1 5.9 8.5 5.9 9.0 5.9
122 5.7 4.9 5.9 4.9 6.5 5.1 7.4 5.6 7.7 5.6 8.1 5.6 8.7 5.6
Low ambient performance with LGRED° heat technology is included in Multi V 5 Air Source Units produced after February 2019.
STANDARD WALL-MOUNTED
Cooling Capacity Tables
ARNU093SJA4
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).
Cooling range with the Low Ambient Baffle Kit (sold separately) installed on the outdoor
unit(s) is -9.9°F to +122°F, and is achieved only when all indoor units are operating in
cooling mode. Does not impact heat recovery system synchronous operating range.
The System Combination Ratio must be between 50–130%.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice.
Current certified ratings are available at www.ahridirectory.org.
For outdoor unit performance data, see the respective outdoor unit performance data
manuals on https://lghvac.com/commercial.