Installation Manual 77
ENGLISH
CAUTION
Product may not properly operate if the relevant DIP switch is not properly setup.
Electrical Wiring
u Checking according to dip switch setting
1. You can check the setting values of the Master outdoor unit from the 7 segment LED.
The dip switch setting should be changed when the power is OFF.
u Checking the setting of the Master unit
The number is sequentially appeared at the 7 segment in 5 seconds after applying the power. This
number represents the setting condition. (For example, represents R410A 30HP)
Master model code Slave1 model code Slave2 model code total capacity 2 25 190
1 ~255 : Master model code
1 ~255 : Slave1 model code
1 ~255 : Slave2 model code
1 ~255 : Slave3 model code
8~54HP(220V) : HP number(sum of master capacity and slave capacity)
* 8~80HP(460V)
No display : cooling only 2 : heat pump / heat recovery
25 : normal
190 : Model Type (ARUB***DT3), 170 : Model Type(ARUB***BT3)
Example) 30HP(ARUB***DT3), R410A
194 193 30 2 25 190
}
Refer to table code
Model Code (220V)
Model Code Unit (HP) Unit Ref.
190 8
191 10
192 12
193 14
194 16
195 18
Master &
Slave
R410A
Model Code (460V)
Model Code Unit (HP) Unit Ref.
190 8
191 10
192 12
193 14
194 16
195 18
196 20
Master &
Slave
R410A