Outdoor units Information
Installation Manual 9
ENGLISH
n Heat Recovery
Power Supply: Outdoor Unit (3Ø, 208/230V, 60Hz)
Unit
System(HP)
Model
Product Charge kg
Max. Connectable No. of Indoor Units
Net Weight kg
lbs
Dimensions (WxHxD) mm
inch
Connecting Pipes
Liquid [mm(inch)]
Low Pressure Gas [mm(inch)]
High Pressure Gas [mm(inch)]
1 Outdoor unit
8 10 12
ARUB80BT3 ARUB100BT3 ARUB120BT3
ARUB80BT3 ARUB100BT3 ARUB120BT3
5 6.4 6.4
13(20) 16(25) 20(30)
190 × 1 240 × 1 240 × 1
418 × 1 529 × 1 529 × 1
(920×1,680×760)×1 (920×1,680×760)×1 (920×1,680×760)×1
(36.2×66.1×29.9)×1 (36.2×66.1×29.9)×1 (36.2×66.1×29.9)×1
9.52(3/8) 9.52(3/8) 12.7(1/2)
19.05(3/4) 22.2(7/8) 28.58(1-1/8)
15.88(5/8) 19.05(3/4) 19.05(3/4)
Unit
System(HP)
Model
Product Charge kg
Max. Connectable No. of Indoor Units
Net Weight kg
lbs
Dimensions (WxHxD) mm
inch
Connecting Pipes
Liquid [mm(inch)]
Low Pressure Gas [mm(inch)]
High Pressure Gas [mm(inch)]
1 Outdoor Unit
14 16 18 20
ARUB140BT3 ARUB160BT3 ARUB180BT3 ARUB200BT3
ARUB140BT3 ARUB160BT3 ARUB180BT3 ARUB100BT3
ARUB100BT3
7.0 7.0 9 12.8
23(35) 26(40) 29(45) 32(50)
270 × 1 270 × 1 330 × 1 240 × 2
595 × 1 595 × 1 727 × 1 529 × 2
(1,240×1,680×760)×1 (1,240×1,680×760)×1 (1,240×1,680×760)×1 (920×1,680×760)×2
(48.8×66.1×29.9)×1 (48.8×66.1×29.9)×1 (48.8×66.1×29.9)×1 (36.2×66.1×29.9)×2
12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8)
28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8) 28.58(1-1/8)
22.2(7/8) 22.2(7/8) 22.2(7/8) 22.2(7/8)
Outdoor units Information
n Combination Ration(50~200%)
Notes: * We can guarantee the operation only within 130% Combination.
If you want to connect more than 130% combination, please contact us and discuss the
requirement like below.
1) If the operation of indoor unit is more than 130%, the airflow is operated as low in the all indoor
units.
2) The number of () means the number of Max. connectable indoor units, when the connected ca-
pacity of indoor units is in the table above.
Outdoor Number Connection Capacity
Single outdoor units 200%
Double outdoor units 160%
Triple outdoor units 130%