Outdoor Unit Functions
SPECIAL CONTROLS
Stop Operation Control
Stop Operation
Component Stop Operation Notes
Inverter Compressor Off -
Fan Stop -
Main EEV 32 Pulse -
Subcooling EEV 16 Pulse Stop (Minimum Pulse)
Four-Way Valve Off -
Stop Operation Control in Cooling Mode
Stop Operation Control in Heating Mode
Component Stop Operation Notes
Inverter Compressor Off -
Fan Stop -
Main EEV 32 Pulse -
Subcooling EEV 16 Pulse Stop (Minimum Pulse)
Four-Way Valve Off When air temperature is >30°C (86°F)
Table 10: Stop Operation Control in Cooling Mode.
Table 11: Stop Operation Control in Heating Mode.
Oil Equalizing Control
Oil equalizing control prevents oil imbalance between the inverter compressors. If the oil level sensors detect different oil levels between the
compressors, then the oil equalizing EEV will open for five (5) minutes.