EasyManua.ls Logo

LG Multi V Standard Gen 4 ARNU123SJA4 - Page 73

LG Multi V Standard Gen 4 ARNU123SJA4
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
73
Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 22: Standard (Gen 4) Wall-Mounted SV Chassis Wiring Diagram Legend
Figure 98: Standard Wall-Mounted (SV Frame) Wiring Diagram
*To enable Generation 4 features, outdoor unit DIP switch no. 3 must be set to ON. Please refer to the Multi V 5, Multi V IV, Multi V Water IV, Multi V
S Engineering Manual for additional information.
PCB Connection Purpose Function
CN-POWER AC Power supply AC Power line input for indoor controller
CN-MOTOR Fan motor output Motor output of BLDC
CN-LEV EEV output EEV control output
CN-U/D Step motor Step motor output
CN-DISP2 Display Display of indoor status
CN-DISP1 Display Display of indoor status
CN-CC Dry contact Dry contact line
CN-485 Communication Connection between indoor and outdoor units
CN-REMO Remote controller Remote control line
CN-EXT1 External ON / OFF controller External ON / OFF controller connection
CN-TH1 Return air and inlet pipe thermistor Return air and inlet pipe thermistor connection
CN-TH2 Outlet pipe thermistor Outlet pipe thermistor connection
CN-TH3 Float switch Float switch connection
Standard Wall-Mounted
SV Frame
ELECTRICAL WIRING DIAGRAM

Related product manuals