WSU PRODUCT DATA | 21
Water Source Unit Product Data
Due to our policy of continuous product innovation, some specications may change without notication.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
Table 9: Triple-Frame 460V Units
Triple Frame 460V Water Source Unit Specications
GENERAL DATA
Combination Unit Model Number
36.0 Ton
ARWM432DAS5
42.0 Ton
ARWM504DAS5
48.0 Ton
ARWM576DAS5
Individual Component Model Numbers
ARWM144BAS5
x 3
ARWM144DAS5 x 1
+ ARWM168DAS5 x 1
+ ARWM192DAS5 x 1
ARWM192DAS5 x 3
Cooling Performance
Nominal Cooling Capacity (Btu/h)
1
430,500 504,000 571,200
Heating Performance
Nominal Heating Capacity (Btu/h)
1
486,000 567,000 648,000
Operating Range (Entering Water Temperature)
2
Cooling (°F)
50 - 113 50 - 113 50 - 113
Heating (°F)
50 - 113 50 - 113 50 - 113
Synchronous Operation (°F)
50 - 113 50 - 113 50 - 113
Compressor
Inverter Quantity
HSS DC Scroll x 3
Oil / Type
PVE / FVC68D
Unit Data
Refrigerant Type
R410A
R410A Refrigerant Factory Charge (lbs)
7.7 + 7.7 + 7.7 7.7 + 9.9 + 9.9 9.9 + 9.9 + 9.9
Refrigerant Control / Location
EEV / Indoor Unit
Max. Number Indoor Units / System
64 64 64
Sound Pressure dB(A)
3
61 (67) 63 (67) 65 (67)
Net Unit Weight (lbs.)
328 + 328 + 328 328 + 348 + 348 348 + 348 + 348
Shipping Weight (lbs.)
346 + 346 + 346 346 + 366 + 366 366 + 366 + 366
Communication Cables
5,6
2 x 18 AWG
Heat Exchanger (Stainless Steel Plate)
Maximum Pressure Resistance (psi)
640 640 640
Flow at Rated Condition (GPM)
35.5 + 35.5 + 35.5 35.5 + 45.7 + 50.7 50.7 + 50.7 + 50.7
Total Heat of Rejection (Btu/h)
570,300 663,600 760,500
Total Heat of Absorption (Btu/h)
440,400 513,200 580,800
Pressure Drop (ft-wg)
9.63 / 9.63 / 9.63 9.63 / 8.32 / 10.08 10.08 / 10.08 / 10.08
Δt
4
(°F)
10.7 10.1 10.0
Piping
7
Liquid Line (in.,OD)
1/2 + 1/2 + 1/2 Braze 1/2 + 5/8 + 5/8 Braze 5/8 + 5/8 + 5/8 Braze
High Pressure Vapor Line (in.,OD)
7/8 + 7/8 + 7/8 Braze 7/8 + 7/8 + 7/8 Braze 7/8 + 7/8 + 7/8 Braze
Low Pressure Vapor Line (Heat Recovery only; in.,OD)
1-1/8 + 1-1/8 + 1-1/8 Braze 1-1/8 + 1-1/8 + 1-1/8 Braze 1-1/8 + 1-1/8 + 1-1/8 Braze
Water Inlet / Outlet Connection (in.,ID)
1-1/2 + 1-1/2 + 1-1/2 FPT 1-1/2 + 1-1/2 + 1-1/2 FPT 1-1/2 + 1-1/2 + 1-1/2 FPT
Condensate Pipe Diameter (in.,ID)
3/4 + 3/4 + 3/4 MPT 3/4 + 3/4 + 3/4 MPT 3/4 + 3/4 + 3/4 MPT
1
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice. Current certified ratings are available at www.ahridirectory.org.
2
Variable water flow control kit PWFCKN000 is required for applications with entering
water temperatures below 590F (one kit per frame). Minimum flow rate must be 40% of the
nominal flow rate, 2-10V signal with a linear flow response valve.
3
Sound pressure levels are tested in an anechoic chamber under ISO 3745 standard
at rated AHRI operating conditions. Sound pressure level may increase during heating
operation at maximum compressor frequency. Value in parenthesis is the maximum sound
pressure at those conditions.
4
Value is calculated as follows: Δt = Total Heat of Rejection ÷ (Rated Flow Rate x 500).
Data is for pure water.
5
Communication cable between WSU, IDU(s) / HRU(s), and Central Controller must be a
minimum of 2-conductor, 18 AWG, twisted, stranded, and shielded. Ensure the
communication cable shield is properly grounded to the WSU chassis only. Do not
ground the communication cable at any other point. Wiring must comply with all applicable
local and national codes.
6
Power wiring is field provided, solid or stranded, and must comply with the applicable
local and national codes.
7
LG requires that LATS software be used on all projects to ensure correct line sizing.
Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG MULTI V WATER 5 ARW Series and is the answer not in the manual?

LG MULTI V WATER 5 ARW Series Specifications

General IconGeneral
BrandLG
ModelMULTI V WATER 5 ARW Series
CategoryHeat Pump
LanguageEnglish

Related product manuals