38 | WSU PRODUCT DATA
MULTI V Water 5 Water Source Unit Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
Ton Model
Sound
Pressure*
Sound
Power
6 ARWM072BAS5 48 (62) 60
8 ARWM096BAS5 50 (62) 62
10 ARWM121BAS5 56 (62) 68
12 ARWM144BAS5 56 (62) 68
14 ARWM168BAS5 52 (65) 65
16 ARWM192BAS5 53 (65) 66
18 ARWM216BAS5 57 (65) 70
20 ARWM240BAS5 59 (65) 72
22 ARWM264BAS5 59 (65) 72
24 ARWM288BAS5 59 (65) 72
30 ARWM360BAS5 61 (67) 75
36 ARWM432BAS5 61 (67) 75
Table 13: Sound Pressure and Sound Power for 208-230V
WSU Models
Measurement taken 3.3′ above finished floor, and at a distance of
3.3′ from face of unit.
Measurements taken with no attenuation and units operating at full
load normal operating condition.
Sound level will vary depending on a range of factors such as
construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
Sound power levels are measured in dB(A)±3.
Tested in anechoic chamber per ISO Standard 3745 at rated AHRI
operating conditions.
3.3ft
3.3ft
Acoustic Data for WSU Models
Figure 5: Sound Pressure Measurement Location.
Ton Model
Sound
Pressure*
Sound
Power
6 ARWM072DAS5 48 (62) 60
8 ARWM096DAS5 50 (62) 62
10 ARWM121DAS5 56 (62) 68
12 ARWM144DAS5 56 (62) 68
14 ARWM168DAS5 58 (62) 70
16 ARWM192DAS5 60 (62) 72
16 ARWM191DAS5 53 (65) 66
18 ARWM216DAS5 57 (65) 70
20 ARWM240DAS5 59 (65) 72
22 ARWM264DAS5 59 (65) 72
24 ARWM288DAS5 59 (65) 72
30 ARWM360DAS5 62 (65) 75
36 ARWM432DAS5 61 (67) 75
42 ARWM504DAS5 63 (67) 77
48 ARWM576DAS5 65 (67) 79
Table 14: Sound Pressure and Sound Power for 460V WSU Models.
ACOUSTIC DATA
Sound Pressure and Sound Power Levels
* Sound pressure level may increase during heating operation at maximum compressor frequency. Value in parenthesis is the maximum
sound pressure at those conditions.