Installation Manual 23
ENGLISH
Thermistors Installation
Fixation of the pipe thermistors (Field work)
1. Fix the thermistor with insulating aluminum tape (Field supply) in order to ensure a good
heat transference.
2. Put the supplied piece of rubber around the thermistor(EBG36949304/05) in order to
avoid loosening of the thermistor after some years.
3. Fasten the thermistor with 2 tie wraps.
4. Insulate the thermistor with the supplied insulation sheet.
INSTRUCTION
Put the thermistor wire slightly top to avoid water accumulation on down of the thermistor.
Make good between thermistor and evaporator. Put the top of the thermistors on the
evaporator, this is the most sensitive point of the thermistor.
1 Most sensitive point of the thermistor
2 Maximize the contact
45°
2
1
Pipe thermistors Installation