124 Trouble Shooting Guide
Self-diagnosis function
3. Self-diagnosis function
Self-Diagnosis Function
Error Indicator
This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of
outdoor unit control board as shown in the table.
If more than two troubles occur simultaneously, lower number of error code is first displayed.
After error occurrence, if error is released, error LED is also released simultaneously.
Display Title Cause of Error
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
Air temperature sensor of indoor unit
Inlet pipe temperature sensor of indoor unit
Transmission error : wired remote
controller indoor unit
Drain pump
Transmission error : outdoor unit
indoor unit
Outlet pipe temperature sensor of
indoor unit
Different operation mode
Indoor LEV
Air temperature sensor of indoor unit is open or short
Inlet pipe temperature sensor of indoor unit is open or short
Failing to receive wired remote controller signal at
indoor unit PCB
Malfunction of drain pump
Failing to receive outdoor unit signal at indoor unit PCB
Outlet pipe temperature sensor of indoor unit is
open or short
Operation mode between indoor unit and outdoor unit
is different
Malfunction of indoor LEV
Indoor unit related error
2
2
2
2
2
1
2
3
4
5
3
3
3
3
2
3
4
5
DC peak
Overcurrent of inverter comp.
Poor voltage charge for driving
INV compressor
High pressure switch
Low/Over voltage
Discharge temperature
(INV compressor A)
Discharge temperature
(INV compressor B)
High pressure
Low pressure
IPM fault or overcurrent to compressor
Overcurrent flows to inverter compressor
DC charging is not performed after starting relay turn
on
System is off by high pressure switch
Input voltage is out of tolerable range.
System is off due to rising of INV compressor A discharge
temperature
System is off due to rising of
INV compressor B
discharge temperature
System is off by excessive increase of high pressure
System is off by excessive decrease of low pressure
Power related error
Compressor related error
Serial No.
Poor fan moto operation
Transmission error : indoor unit
main PCB of outdoor.
In the case that the serial number marked on EEP-
ROM of indoor unit is 0 or FFFFFF
Disconnecting the fan motor connector/Failure or
indoor fan motor lock.
When the addressing signal doesn't come out for 3mins. suddenly, while
the indoor unit gets the calling signal coming from the outdoor unit.