Service Manual 99
Function
3.2 Discharge temperature control
3.3 Inverter protection control
System stopCurrent 23A
item control
Inv compressor 5Hz down/3 secCurrent 20A
Inv. compressor no frequency up
Current 17A
Inv. Compressor normal controlCurrent 17A
System stopDC Peak
System stopHigh pressure switch
System stopLow voltage
<
<
<
<
Off indoor unit LEV 130 (Only
Heating mode)
Ending : Td 65°C
Td 70°C
Do not increase Hz
Ending :Td 95°C
Td 102°C
1~5% down / 30 sec.
After operating in 20+20Hz for 60sec.
System off/restart after 3min.
ending: Td <101°C for 30sec.
Td 106°C
5% open
(every control time)
Td 110°C
(low press. 529kPa)
Liquid gathering
operation(heating)
ending : Td < 103°C
Td 108°C
Control LEV to set
Subcooler out temp. evaporating
temp = 8°C(only heating mode &
Main LEV 800pls)
+10pulse / 10sec.
(only cooling mode)
Subcooler LEV
Td > 85°C
Adjust target suction
superheat 1.5°C, minimum
suction superheat
0.5°C (only heating mode)
Td > 95°C
5% open
(every control time)
Td 105°C
(low press. > 529kPa)
Decrease Indoor superheat
Ending : Td < 95°C
Td 100°C
Main LEV Indoor Unit
System Stop
Td 115°C
Comp
Discharge Temp.