98 Outdoor Unit
3.1.2 Pressure control on heating mode
High pressure control
Low pressure control
Frequency holding
Normal control
OnStopStopPd 3513Pa
On
-5Hz/2sec.-5Hz/2sec.Pd 3317 kPa
Pd 3186 kPa
off
Normal control
Pd Target press -5
Hot gasFanCompressorPressure Range
Normal control
Frequency
holding
Ps 216 kPa
Normal control
Ps 242 kPa
OffPs 281 kPa
+10Hz/2sec.-5 Hz/2sec.
Ps 203 kPa
before 1min
On
StopStop
Ps 203 kPa
after 1min
Hot gasFanCompressor
Pressure Range