Troubleshooting Guide
160 Outdoor Unit
Excessive low
pressure drop
Error
Code
Error Contents Meaning Main Causes
Error display
position
35
Comp. off due to the low
pressure sensor
Concerned
Remote con-
troller
Panel Display
Outdoor unit
1. Defective low pressure sensor
2. Defective Indoor / Outdoor Unit fan
3. Refrigerant shortage or leakage
4. Pipe shape change due the dam-
age
5. Defective indoor outdoor LEV
6. Covering or chocking (Outdoor cov-
ering during the cooling mode /
Indoor filter chocking during the
heating mode)
7. SVC valve chocking
8. Defective outdoor PCB
9. Defective indoor pipe temp. sensor
■ Defect inspection method
1) Check the indoor and outdoor fan and replace if required. (Refer to CH105~CH108)
2) Check if the proper heat exchange is obtained in Indoor and Outdoor Unit
Otherwise, modify the installation condition to get the proper heat exchange.
Remove the outdoor cover (by dust etc) if any and also check the Indoor Unit filter also.
3) Check the SVC valve open and pipe condition (bent, dent etc ) .
4) Check whether the actual low pressure is excessively low.
Connect the manifold gauge to the svc valve and compare the low pressure reading.
5) Check the Indoor / Outdoor Unit LEV connector connecting condition .
6) Check the LEV / Hot gas valve's coil resistance
LEV : Resistance between each terminal of the LEV 45~90Ω
hot gas :
liquid injection :
In case the coil resistance is normal, then please check the LEV / Hot Gas Valve.
(Refer to Check!!)
7) Recalculate the refrigerant charging and check the charging condition.
8) Check the Indoor Unit pipe temp. sensor connecting condition and temp. sensor resistance.
(Resistance measurement method : Refer to CH02/CH06)
9) In case the above given contents are normal, then please replace the outdoor PCB.
10) In case a similar error code exists even after the replacement of the PCB, then replace the high pressure sen-
sor.