Service Manual 163
Troubleshooting Guide
Low pressure sen-
sor error
Error
Code
Error Contents Meaning Main Causes
Error display
position
42
Sensor measured value is
not normal
(Open / Short)
Concerned
Remote con-
troller
Panel Display
Outdoor unit
1. Defective low pressure sensor con-
nector
2. Defective low pressure sensor
(Open/Short)
3. Defective outdoor PCB
High pressure
sensor error
Error
Code
Error Contents Meaning Main Causes
Error display
position
43
Sensor measured value is
not normal (Open/Short)
Concerned
Remote con-
troller
Panel Display
Outdoor unit
1. Defective high pressure sensor
connector
2. Defective high pressure sensor
error (Open/Short)
3. Outdoor PCB defect
Defect inspection method
1) Check the pressure sensor connecting condition and lead wire connecting condition.
2) In case the above condition is normal then replace the outdoor PCB .
3) If the error code persists even after the replacement of PCB then replace the concerned pressure sensor