2 PARAMETER CODE (HEX)
<Common> Area accessible regardless of inverter models (Note 3)
Parameter
Address
Parameter Name Unit Read/Write Data Value (Hex)
0x0000 Drive model - R 4: SV-iS5
0x0001 Drive capacity - R
0: 0.75 1:1.5 2:2.2 3: 3.7
4: 5.5 5: 7.5 6: 11 7: 15
8: 18.5 9: 22 A: 30 B:37
C:45 D: 55 E: 75 F: 90
10: 110 11: 132 12: 160
13: 200 14:220 15:280
16:375 (Unit : kW)
0x0002 Drive Input Voltage - R 0: 220V 1: 440V
0x0003 S/W Version - R
0100: Ver. 1.00,
0101: Ver 1.01
0x0005 Frequency Reference 0.01Hz R/W
0x0006 Run Command - R/W
Bit 0: Stop
Bit 1: Forward Run
Bit 2: Reverse Run
Bit 3: Fault Reset
Bit 4: Emergency Stop
0x0007 Acceleration Time 0.1 sec R/W
0x0008 Deceleration Time 0.1 sec R/W
0x0009 Output Current 0.1 A R
0x000A Output Frequency 0.01 Hz R
0x000B Output Voltage 0.1 V R
0x000C DC Link Voltage 0.1 V R
0x000D Output Power 0.1 kW R
0x000E Sequence Monitor - R
BIT 0 : Stop
BIT 1 : Forward Run
BIT 2 : Reverse Run
BIT 3 : Fault (Trip)
BIT 4 : Accelerating
BIT 5 : Decelerating
BIT 6 : Output Frequency
Arrival