EasyManuals Logo

LG SV-iS5 User Manual

LG SV-iS5
19 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
modbus-rtu iS5 manual.doc
7
Parameter
Address
Parameter Name Unit Read/Write Data Value (Hex)
BIT 7 : DC Braking
BIT 8 : Stopping
BIT 9 :Not Available
BIT 10 : BrakeOpen
BIT11: Forward Run
Command
BIT 12 : Reverse Run
Command
0x000F Trip information - R
Bit 0:OCT1, Bit 1: OV, Bit 2:
EXT-A Bit 3: BX, Bit 4:OCT2,
Bit 5: GF, Bit 6: OH, Bit 7:
ETH, Bit 8: OLT, Bit 9: HW-
diag, Bit10:EXT-B, Bit11:FO
Bit12:OPT, Bit13:PO
Bit,14:IOLT, Bit15:LV
0x0010 Input Terminal Status - R
Bit 0: P1, Bit 1: P2, Bit 2: P3
Bit 3: P4, Bit 4: P5, Bit 5: P6,
Bit 6: RST, Bit 7: BX, Bit 8:
JOG, Bit 9: FX, Bit 10: RX
0x0011
Output Terminal
Status
- R
Bit 0: Q1 (OC1), Bit 1: Q2
(OC2) Bit 2: Q3 (OC3), Bit 3:
AUX Bit 4: 30AC
0x0012 V1 - R 0 – FFC0
0x0013 V2 - R 0 – FFC0
0x0014 I - R 0 – FFC0
0x0015 RPM - R
(Note 3)
The changed value in Common affects the current setting but returns to the previous setting when
power is cycled or Inverter is reset. However, changing value is immediately reflected in other parameter groups
even in the case of Reset or Power On/Off.
< DRV Group >
Address NO. Description Default Maximum Minimum Unit
5100 DRV#00 Cmd. freq 0 MaxFreq 0 0.01Hz
5101 DRV#01 Acc. Time 100 6000 0 0.1sec
5102 DRV#02 Dec. Time 200 6000 0 0.1sec
5103 DRV#03 Drive mode 1 2 0
5104 DRV#04 Freq. mode 0 4 0

Other manuals for LG SV-iS5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG SV-iS5 and is the answer not in the manual?

LG SV-iS5 Specifications

General IconGeneral
BrandLG
ModelSV-iS5
CategoryController
LanguageEnglish

Related product manuals