modbus-rtu iS5 manual.doc
9
Address NO. Description Default Maximum Minimum Unit
5227 FU1 #39 Energy save 0 30 0 %
5232 FU1 #50 ETH select 0 1 0
5233 FU1 #51 ETH 1min 180 200 ETH Cont %
5234 FU1 #52 ETH Cont 100 150 50 %
5235 FU1 #53 Motor type 0 1 0
5236 FU1 #54 OL level 150 150 30 %
5237 FU1 #55 OL time 100 300 0 0.1sec
5238 FU1 #56 OLT select 1 1 0
5239 FU1 #57 OLT level 180 200 30 %
523A FU1 #58 OLT time 600 600 0 0.1sec
523B FU1 #59 Stall prev. 0 7 0
523C FU1 #60 Stall level 180 250 30 %
< FU2 Group >
Address NO. Description Default Maximum Minimum Unit
5307 FU2 #07
Dwell freq 500 maxFreq StartFreq 0.01Hz
5308 FU1 #08 Dwell time 0 100 0 0.1sec
530A FU2 #10
Jump freq 0 1 0
530B FU2 #11
jump lo 1 1000 jump Hi 1 StartFreq 0.01Hz
530C FU2#12
jump Hi 1 1500 maxFreq jump Lo 1 0.01Hz
530D FU2 #13
jump lo 2 2000 jump Hi 2 StartFreq 0.01Hz
530E FU2 #14
jump Hi 2 2500 maxFreq jump Lo 2 0.01Hz
530F FU2 #15
jump lo 3 3000 jump Hi 3 startFreq 0.01Hz
5310 FU2 #16
jump Hi 3 3500 maxFreq jump Lo 3 0.01Hz
5311 FU2 #17 Start Curve 40 100 1 %
5312 FU2 #18 End Curve 40 100 1 %
5313 FU2 #19 Trip select 0 3 0 BIT
5314 FU2 #20
Power-on run 0 1 0
5315 FU2 #21
RST restart 0 1 0
5316 FU2 #22
Speed Search 0 15 0 BIT
5317 FU2 #23
SS Sup-Curr 100 200 80
5318 FU2 #24
SS P-gain 100 9999 0
5319 FU2 #25
SS I-gain 1000 9999 0
531A FU2 #26
Retry number 0 10 0
531B FU2 #27
Retry delay 10 600 0 0.1sec
531E FU2#30
Motor select 0 9 0
531F FU2#31
Pole number 4 12 2
5320 FU2 #32
Rated-Slip (Note4) 1000 0 0.01Hz