- 37 -
• Function Code 2A : Miscellaneous setting
- Value #1 of Function Code 2A : determine electric heater and sanitary tank heater on and off.
- Value #2 of Function Code 2A : not used.
- Example : If Value #1 is set as ‘0’, then electric heater and sanitary tank heater are on and off according to con-
trol logic. If Value #1 is set as ‘1’, then electric heater is never turned on and only water heater is on and off ac-
cording to control logic.
• Function Code 2B : Sanitary water heating timers
Determine following time duration : operation time of sanitary tank heating, stop time of sanitary tank heating, and
delay time of sanitary tank heater operating.
- Value #1 of Function Code 2B : This time duration defines how long time sanitary tank heating can be continued.
- Value #2 of Function Code 2B : This time duration defines how long time sanitary tank heating can be stopped. It
is also regarded as time gap between sanitary tank heating cycle.
- Value #3 of Function Code 2B : This time duration defines how long time sanitary tank heater will not be turned
on in sanitary water heating operation.
- Example of timing chart :