- 57 -
3. Trouble Shooting Guide
Check Point
1. Unplug the sensor on PCB(Heater).
2. Estimate the resistance of each sensor.
3. If the resistance of the sensor is 10 KΩ / 5 KΩ at 25°C, then sensor is normal.
4. If the resistance of the sensor is 0 KΩ or ∞, then sensor is abnormal. ’ Change the sensor.
5. Plug the sensor on PCB(Heater) and Power ON.
6. Estimate the voltage of each sensor.
7. If the voltage of the sensor is 2.5Vdc at 25°C, then sensor is normal.
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. ’ Repair or Change the PCB(Heater).
of each sensor.
Repair or Change the PCB.
of each sensor.
Display
code
Title Cause of error Check point & Normal condition
01
Remote room
air sensor
• Connector connection error
• Faulty PCB(Heater)
• Faulty sensor (Open / Short)
Normal resistor : 10KΩ/ at 25˚C (Unplugged)
Normal voltage : 2.5Vdc / at 25˚C(Plugged)
Refer to sensor resistance table.
02
Refrigerant
inlet pipe sen-
sor
• Connector connection error
• Faulty PCB(Heater)
• Faulty sensor (Open / Short)
Normal resistor : 5KΩ/ at 25˚C(Unplugged)
Normal voltage : 2.5Vdc / at 25˚C(Plugged)
Refer to sensor resistance table.
06
Refrigerant
outlet pipe
sensor
• Connector connection error
• Faulty PCB(Heater)
• Faulty sensor (Open / Short)
Normal resistor : 5KΩ/ at 25˚C(Unplugged)
Normal voltage : 2.5Vdc / at 25˚C(Plugged)
Refer to sensor resistance table.