- 72 -
23
DC Link High / Low Volt
• DC Link Voltage is
above 420Vdc
• DC Link Voltage is
below 140Vdc
• Check CN_(L), CN_(N) Connection
• Check Input Voltage
• Check PCB DC Link voltage sensor parts
Display
code
Title Cause of error Check point & Normal condition
n Error Diagnosis and Countermeasure Flow Chart
PCB assembly 1
Power connection normal?
No
Check connection from terminal block to
PCB assembly 1 CN(L), CN(N)
Yes
Is input voltage normal ?
No
Yes
Is PCB(Inverter) Normal?
No
Replace PCB assembly 1
Recheck power and installation
condition
Yes
Check L~N Voltage is 230V±15%
WARNING
Before checking PCB(Inverter) or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby
state of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other
parts.