- 79 -
29
Inverter compressor over
current
Inverter compressor input
current is over 30A
1. Overload operation
(Pipe clogging/Covering/EEV defect/Ref.
overcharge)
2. Compressor damage(Insulation damage/Motor
damage)
3. Input voltage low
4. ODU PCB assembly 1 damage
Display
code
Title Cause of error Check point & Normal condition
n Error Diagnosis and Countermeasure Flow Chart
Is installation
condition normal?
No
Yes
Yes
Yes
Recheck power and installation condition
1. Check Pipe clogging/distortion
2. Check Covering (Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
Reassemble or manage if abnormality found
Yes
Is input voltage normal?
No
Check
U-V,V-W,W-U phase is 220~240 V ±10%
Check connection condition and wiring if power is
abnormal
Yes
Is PCB assembly 1
normal?
No
Check PCB assembly 1 IPM normality
Replace inverter PCB assembly
Are the resistance
between each phase and
insulation resistance of Inverter
compressor normal?
No
1. Check resistance between each terminal of compressor
(0.188 ±7%)
2. Check insulation resistance between compressor
terminal and pipe (over 50 MΩ)
Replace compressor if abnormality found
Is compressor
wire connection
condition normal?
No
1. Check PCB assembly 1 U,V,W connector
connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
Reassemble if abnormality found
Check Flow Chart
WARNING
Before checking PCB(Inverter) or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby
state of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.