- 88 -
62
Heatsink High error
220-240 V~ heatsink
temperature is over 85°C
1. ODU fan locking
2. Heatsink assembly of PCB assembly 1 condition
abnormal
3. Defect of temperature sensing circuit part defect
of INV PCB(Inverter)
Display
code
Title Cause of error Check point & Normal condition
n Error Diagnosis and Countermeasure Flow Chart
Is installation 
condition normal ?
No 
Yes 
1. Check fan locking
2. Check covering of heat exchanger
3. Check distance between ODU and obstacles
4. Check pipe distortion and abnormality
5. Check service valve is opened
→ Eliminate causes for abnormal condition
Check resistance between NO.19 pin and NO.20 pin 
of PFC module 
→ Replace PCB(Inverter) if abnormality found
Is assemble condition 
of INV PCB(Inverter)
heatsink normal ?
Is PCB(Inverter) temperature 
sensing part normal ?
No 
No 
Yes 
Check assemble condition between INV PCB(Inverter) 
heatsink and PFC & IPM module → Reassemble if 
abnormality found
Recheck installation condition
and connection of Heat sink
Yes 
Check Point
1. Check resistance between No.19 pin and NO.20 pin of PCB PFC module
2. Resistance value should be in 7kΩ ±10%.(at 25°C).