- 92 -
73
AC input instant over
current error
(Matter of software)
PCB(Inverter) input
power current is over
48A(peak) for 2ms
1. Overload operation (Pipe clogging/Covering/EEV
defect/Ref.overcharge)
2. Compressor damage
(Insulation damage/Motor damage)
3. Input voltage abnormal (L, N)
4. Power line assemble condition abnormal
5. PCB assembly 1 damage
(input current sensing part)
Display
code
Title Cause of error Check point & Normal condition
n Error Diagnosis and Countermeasure Flow Chart
No
1.Check Pipe clogging/distortion
2.Check Covering (Unit)
3.Check EEV connector assemble condition/normal operation
4.Check refrigerant pressure
Reassemble or manage if abnormality found
Is installation
condition normal?
Is compressor
Wire connection
condition normal?
1.Check PCB assembly 1 U,V,W connector connection condition
2.Check wire disconnection and wiring
3.Check compressor terminal connection condition(bad contact)
Reassemble if abnormality found
Is AC input Wire connection
condition normal?
1.Check R,S,T connection condition
2.Check wire disconnection and wiring
Reassemble if abnormality found
PCB assembly 1
normal?
Yes
No
Recheck power and
installation condition
Yes
Yes
Yes
No
No
Yes
No
Check
R-S, S-T, T-R phase voltage is 220~240 V ± 10%
Check connection condition and wiring if power is abnormal
Is input voltage normal?
Check PCB assembly 1 IPM normality
Replace PCB assembly 1