6. Wait 1-2 minutes before plugging the input cord (500-3000VA) or closing the input breaker (5-10
kVA) to restart the UPS. Leave the UPS in standby mode at this time so that the customizable
settings can be restored.
7. If using the LCD, navigate to Main menu/Configuration/UPS and change any setting to match
what was recorded in step 2. Then navigate to Main menu/Configuration/Battery and change
any setting to match what was recorded in step 2.
If using the configuration program, restart the configuration program and use the “UPLOAD”
button and point to the saved configuration file that you saved in step 2.
8. Restart the UPS. Navigate to Main menu/Control/Turn ON & OFF, press the ENTER button,
select TURN UPS ON and press ENTER and confirm to turn on the UPS.
If using an external MicroPOD on the 500-3000VA, once the UPS available light is illuminated,
rotate the rotary switch to the UPS position.
If using any external maintenance bypass on the 5-10 kVA models, the unit will only start on its
internal bypass, then follow the transfer sequence to transfer from maintenance bypass to UPS.
All connected equipment should now be back on protected power by the UPS inverter.
9. If you did not have any external maintenance bypass, once the UPS has restarted, restart all the
connected equipment.