Operating Range
3--3
Liebert HPC---S 006---022---PD---273571---01.03.2012
Tab. 3e --- Operating range --- Freecooling with AC fans 900mm
Models: FB0 006---022 006 007 009 011 014 015 018 019 022
Operating range
Max. outdoor temperature
(1)
°
C 50.0 47.0 53.0 51.0 48.5 46.5 50.0 48.5 47.0
Safety devices settings
High pressure switch
(1)
High pressure safety valve
HP safety valves (each circuit)
High pressure safety valve connection
Low pressure switch
barg
barg
Nr.
inch
barg
42
45
1
3/4” G
4.4
(1) --- With nominal air flow; mixt ure outlet temperature 10° C; full load; R410A refrigerant.
Tab. 3f --- Operating range --- Freecooling with AC fans 800mm
Models: FB0 006---022 006 007 009 011 014 015 018 019 022
Operating range
Max. outdoor temperature
(1)
°
C 48.5 45.5 52.0 49.5 46.5 44.0 48.5 46.5 45.0
Safety devices settings
High pressure switch
(1)
High pressure safety valve
HP safety valves (each circuit)
High pressure safety valve connection
Low pressure switch
barg
barg
Nr.
inch
barg
42
45
1
3/4” G
4.4
(1) --- With nominal air flow; mixt ure outlet temperature 10° C; full load; R410A refrigerant.
Tab. 3g --- Operating range --- Freecooling with EC fans 900mm
Models: FG0 006---018 006 007 009 011 014 015 018
Operating range
Max. outdoor temperature
(1)
°
C 51.5 55.0 55.0 52.5 54.5 53.0 52.0
Safety devices settings
High pressure switch
(1)
High pressure safety valve
HP safety valves (each circuit)
High pressure safety valve connection
Low pressure switch
barg
barg
Nr.
inch
barg
42
45
1
3/4” G
5
(1) --- With nominal air flow; mixt ure outlet temperature 10° C; full load; R410A refrigerant.
Tab. 3h --- Operating range --- Freecooling with EC fans 800mm
Models: FG0 006---018 006 007 009 011 014 015 018
Operating range
Max. outdoor temperature
(1)
°
C 45.5 51.5 50.5 46.5 49.5 47.5 45.5
Safety devices settings
High pressure switch
(1)
High pressure safety valve
HP safety valves (each circuit)
High pressure safety valve connection
Low pressure switch
barg
barg
Nr.
inch
barg
42
45
1
3/4” G
5
(1) --- With nominal air flow; mixt ure outlet temperature 10° C; full load; R410A refrigerant.