Operating Range
3--1
Liebert HPC---S 006---022---PD---273571---01.03.2012
Oper atin g Rang e
Working Limits
Minimum temperature of outdoor air entering condenser coils (with standard operating unit):
---25 ° C for Freecooling models;
---1CforChillermodels.
Maximum outdoor air temperature is in relation to each model, as indicated in the following tables.
High water flow values (corresponding to a thermal difference at the evaporatorlower than 3.5° C --- C)
may cause corros i ons and vibrations inside the plate heat exchanger and in the hydraulic circuit.
The Minimum water flow allowed corresponds to a maximum temperature difference of C.
More extreme operating conditions would active safety devices and the unit would be stopped.
The outlet water temperature must range from C to 15° C.
The maximum allowed water return temperature, when the unit is in full operation, is 20° C; returntemper-
atures over 20° C are allowed only during start---up.
The “G” version with EC fans 900mm (digit 11 = C) admit Maximum Outlet Water Temperature of 20 ° C
and Maximum Water Return Temperature of 26° C when the units are at full power.
The maximum permitted glycol percentage is 50% (35% with standard pump groups fitted).
The necessary minimum glycol percentage depends on the minimum ambient air temperature condi-
tions referred to the place of installation.
The maximum hydraulic working pressure is 6 barg (safety valve set at 6 barg, optional).
Nominal power supply tolerance: 400V
+
/
---
10%; max. voltage unbalance: 2%.
See “Operation range” table reporting the limits for each model; for different values ask your agent.
All the working limits indicated in both diagrams and tables refer to steady---state operation mode.
Unit storage conditions:
D between ---10 ° C and + 45 ° C for all models; humidity: 80% R.H. non-condensing.
60
A v e r a g e H P C --- S 0 0 6 --- 0 2 2 W o r k i n g L i m i t s
Ambient Temperature (_C)
LWT (_C)
25
5550454035302520151050--- 5--- 10--- 15--- 20--- 25--- 30
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Only
Gmodels
All models
Freecooling
only
Gmodels
Freecooling
only
All models
This diagram shows the average working limits of all the products family.
Refer to table 3 for the working limits of each unit.