8
Sound Levels
8--1
Liebert HPC---S 006---022---PD---273571---01.03.2012
Sound Levels
Sound Pressure and Power Levels
SPL
The values of Sound PressureLevel SPL for every octave band frequency, measured with unit on full load
operation, at nominal working conditio ns (ambient air temperature 35_C, evaporator water inlet/outlet
temperature 12/7_C), free field conditions and 1 m from unit in according to ISO 3744 average method
are indicated in the following tables.
PWL
The values of Power Level PWL for every octave band frequency, with unit on full load operation, at nom-
inal working conditions (ambient air temperature 35_C, evaporator water inlet/outlet temperature
12/7_C), calculated in according to ISO 3744 procedure method are indicated in the following tables.
Tab. 8a --- SPL CB0 --- FB0 900AC
Models Octave band frequency [ Hz ] Tota l
[dB(A)]
“SPL Sound Pressure Levels [dB]
63 125 250 500 1000 2000 4000 8000
CB0006 FB0006 70 73 73 73 71 65 59 56 75.0
CB0007 FB0007 70 73 73 73 71 65 59 56 75.0
CB0009 FB0009 71 74 74 74 72 66 60 57 76.0
CB0011 FB0011 74 74 74 74 72 67 60 57 76.0
CB0014 FB0014 75 75 74 74 72 69 61 58 76.5
CB0015 FB0015 75 75 74 74 72 69 61 58 76.5
CB0018 FB0018 75 75 74 74 73 69 62 59 77.0
CB0019 FB0019 76 75 75 74 74 69 63 59 77.5
CB0022 FB0022 77 75 76 75 74 70 63 60 78.0
Tab. 8b --- PWL CB0 --- FB0 900AC
Models Octave band frequency [ Hz ] Tota l
[dB(A)]
“PWL Sound Power Levels [dB]
63 125 250 500 1000 2000 4000 8000
CB0006 FB0006 87 90 90 90 88 82 76 73 92.0
CB0007 FB0007 87 90 90 90 88 82 76 73 92.0
CB0009 FB0009 89 92 92 92 90 84 78 75 94.0
CB0011 FB0011 92 92 92 92 90 85 78 75 94.0
CB0014 FB0014 93 93 92 92 90 87 79 76 94.5
CB0015 FB0015 93 93 92 92 90 87 79 76 94.5
CB0018 FB0018 94 94 93 93 92 88 81 78 96.0
CB0019 FB0019 95 94 94 93 93 88 82 78 96.5
CB0022 FB0022 96 94 95 94 93 89 82 79 97.0
Note:
Sound power levels tolerance for each octave band: --- 0/+2 dB