Model Number Description
2--2
Liebert HPC--- S 006--- 022--- PD--- 273571--- 01.03.2012
Kits / Accessories shipped loose
D Anti-vibrating mounts (spring or rubber)
D Dee shackle UNI 1947
D Coldfire IP40 remote box
D W ater filter
Configuration Rules
In order to give the units the highest flexibility and a high option number, it is necessary to follow
the configuration rules indicated here below, so as to select the unit with all compatible options:
Rule valid for all Chiller and Freecooling versions:
Compressor soft starter are not electrically compatible with compressors power factor correc-
tions
D if digit 8 = 1 than digit 16 = 0
on digit 11: A & B not available on G version (default: A with Base version and C with G ver-
sion)
Rules valid for Chiller versions only ( on Freecooling chillers electric heaters are
not available):
Heating resistors have to be selected according to the presence of the pumps, tank, etc.
D if digit 15 = 1 or 2, then digit 10 = 0 or 2
D if digit 15 = 1, then digit 12 = 2, 3, 4 or 5
D if digit 15 = 2, then digit 12 = 1
D ifdigit10=2,thendigit15=1or2