Precision Cooling
For Business-Critical Continuity™
Liebert VFD Condenser — Model TCDV
Product Information Manual - 50/60Hz
Question and Answer IconNeed help?

Do you have a question about the Liebert TCDVTM and is the answer not in the manual?

Liebert TCDVTM Specifications

General IconGeneral
BrandLiebert
ModelTCDVTM
CategoryHeat Pump
LanguageEnglish

Summary

1.0 Introduction

1.1 Description

The Liebert VFD Control Condenser, Model TCDV, is an air cooled direct-drive refrigeration condenser designed to reject heat.

1.2 Application

The VFD Control Condenser is applied to precision air conditioning units with dual refrigeration circuits, including units with digital scroll compressors.

1.3 Features and Benefits

Details the Variable Frequency Drive (VFD) control, EMC filter, inverter duty motor, transducers, TVSS, locking disconnect, and alarm contacts.

2.0 Dimensional and Electrical Data

3.0 Guide Specifications

3.1 General

Condenser construction: housing, coil, fans, motors, guards, electrical controls, and mounting legs. Power supply details.

3.2 Coil

Liebert manufactured coil: copper tubes, staggered pattern, corrugated aluminum fins, Type 'L' headers, factory leak-tested and dehydrated.

3.3 Fans

Aluminum blades, corrosion-protected steel hubs, heavy-duty keyed hub, dual setscrews. 26" diameter or less, factory balanced.

3.4 Fan Motors

Inverter duty motors, ceramic bearings, overload protection, rain slingers, permanently lubricated bearings, galvanized steel supports.

3.5 Head Pressure Control

VFD control, 0-100% RPM, pressure transducers, ambient thermostats, motor overload, electrical control circuit. Operates to -20°F.

3.6 Housing

Bright aluminum sheet, divided into fan sections by baffles. Galvanized steel structural members. Aluminum legs with rigging holes.

3.7 TVSS and Unit Disconnect Switch

Transient Voltage Surge Suppression and locking disconnect are factory-installed and wired in the enclosed electrical panel.

3.8 Alarm Contacts

Normally open, dry contacts are provided for indication of VFD and TVSS alarm conditions.

3.9 Electrical Controls

Connections and controls in a weatherproof enclosure, integral with the condenser for appearance and protection.