EasyManua.ls Logo

Liebert UPS System - Page 45

Liebert UPS System
121 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Commissioning of UPS
39
2001-11-08
UL33-0400L
12:50:30
Inv. On Units 2/4 ID: 1
Input Breaker Closed
11£ -08 12:09
UPS in Battery Mode
Battery low
11£ -08 12:09
11£ -08 12:28
11£ -08 12:28
11£ -08 12:50
Records
Out
System
Local
Settings
Byp. Breaker Closed
Mains Volt. Abnormal
Battery
Chinese
Chinese
English
Com. Adress Set
1
1
Date & Time Set
2001£ -11£ -08 12:50:30
Language
m
Fig. 4-2 Setup Language
Manual Battery Self Test : Select “start self test” or “stop self test”
Contrast Adjustment : Change the display contrast according to the 11 bars, as
shown in Figure 4-4.
2001-11-08
UL33-0400L
12:50:30
Inv. On Units 2/4 ID: 1
Input Breaker Closed
11£ -08 12:09
UPS in Battery Mode
Battery low
11£ -08 12:09
11£ -08 12:28
11£ -08 12:28
11£ -08 12:50
Records
Out
System
Local
Settings
Byp. Breaker Closed
Mains Volt. Abnormal
Battery
m
ÊÖ¶¯µç³Ø×Ô¼ì
Start
Stop
Display contrast adjust
Record Query Range
3 days
0: all records
Manual Batt Test
Fig. 4-4 Manual Battery Self-test
History Record : The set range is 1-30 days. If “0” is set, all records will be
available for viewing.
Background Communication Setup : select between modem and RS232, as shown
in Figure 4-5
Baud Rate setup : Select from available baud rates of 9600, 4800, 2400 or 1200,
as shown in Figure 4-5
Callback time setup : the available set range is from 1-5 times, as shown in Figure
4-5

Table of Contents

Related product manuals