Verify equipment integrity and type conformity upon unpacking.
Emphasizes trained personnel, electrical safety protocols, and adherence to operational procedures.
Highlights risks from charged capacitors and the necessity of qualified personnel for handling.
Displays device version code at startup, useful for fault reporting.
Defines terms: four quadrant regulators, FCP program, stages, and steps.
Details the FCP program's role in minimizing switching operations and equalizing stage usage.
Measures coso and controls capacitor connection/disconnection for power factor regulation.
MCE06ADV features 6 relay outputs; MCE12ADV features 12 relay outputs.
Highlights FCP regulation, switching programs, four quadrant control, LCD display, and easy setup.
Describes the front cover, screen, configurable parameters, measured parameters, and navigation keys.
Directs users to Section 6 for detailed setup, parameter description, and control modes.
Explains the LCD screen, icons for status (RUN, inductive/capacitive), and stage indication.
Lists parameters displayed in RUN mode: coso, current, THD, voltage, and maximum values.
Details error codes (E00-E05) and their corresponding descriptions for troubleshooting.
Explains the alarm relay's configuration and behavior during error conditions.
Defines the two operating statuses: RUN (normal operation) and Set-up (configuration).
Describes keys for entering set-up mode and manual stage connection/disconnection.
Details key functions for menu navigation, value adjustment, and saving changes.
Highlights risks from charged capacitors and the necessity of qualified personnel for handling.
Summarizes supply voltage, current measurement, protections, and reference standards.
Specifies mounting requirements and fitting hole dimensions according to DIN 43 700.
Details wiring, safety precautions, CT installation, and voltage/current measurement connections.
Illustrates correct CT placement and highlights consequences of incorrect connections.
Specifies cable sizes for supply/relays and required circuit protection.
Diagram showing terminal functions for MCE06ADV, including supply and relay outputs.
Diagram showing terminal functions for MCE12ADV, including supply and relay outputs.
Sets the desired power factor (coso) for the installation, adjustable from 0.85 inductive to 0.95 capacitive.
Defines the reactive current of the smallest capacitor step, dependent on CT ratio and supply voltage.
Provides a method to calculate the C/K value for conditions not covered in Table 5.1.
Sets capacitor stage power ratings using programs like 1:1:1 or 1:2:2.
Configures delay times (Tc) between stage connections and re-connection delay (Tr).
Allows selection of total capacitor stages (up to 6 for MCE06ADV, 12 for MCE12ADV).
Adapts regulator to different voltage/current measurement phase configurations (T1-T6).
Sets the primary current rating of the CT used for installation current measurement.
Explains the procedure to enter the set-up mode using a long key push.
Provides a visual guide to navigating menu options and changing parameters.
The normal operating state where the regulator performs PF correction automatically.
Indicates abnormal situations, displaying error codes and potential device actions.
Details manual stage control, parameter measurement, and clearing maximum values.
Explains device behavior and potential causes for different error codes during alarm conditions.
States no special maintenance is required, but work must be done by qualified staff.
Provides contact information for INTERNATIONAL CAPACITORS, S.A. technical support.