FlexPower Vantage Standard Power System - Installation Manual 10
1. The power supply must be installed within the protected area.
2. The LifeSafety Model EB-80 must be used to house the required battery(ies) when capaaacites of 40 to 80Ah are required. The
EB-80 shall be mounted within 6ft of the power supply and the wiring enclosed in conduit.
3. Connections to the SYS FLT, AC FLT, and FAI inputs shall be completed within the same room, not exceeding a length of 3m.
4. Do not connect equipment to an AC power source that is controlled by a switch.
5. The power supplies shall be mounted in a Listed LifeSafety Power enclosure.
6. Trouble contacts shall be monitored by a listed alarm system.
The following sections cover specific requirements based on application:
UL1076, Proprietary Burglar Alarm Applications:
1. The LifeSafety tamper switch must be employed to monitor the power supply.
2. To achieve 4 hours of standby at full load current, 80Ah min. battery capacity is required for the FPV102 or FPV104. To achieve 4
hours of standby at full load current, 40Ah min. battery capacity is required for the FPV4 and FPV6.
S319, Access Control Applications:
1. The LifeSafety tamper switch must be employed to monitor the power supply.
For UL Compliance:
Any locking device shall be configured for fail safe operation upon occurrence of an alarm as shown in Activation with a Normally
Closed Relay Contact in page 6, FAI Input Usage.
General Applications
© 2019 LifeSafety Power Inc.P03-057Rev A0507/19
IMPORTANT
All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each
product for their particular application. LifeSafety Power makes no warranties as to the accuracy or completeness of the information,
and disclaims any liability regarding its use. LifeSafety Power’s only obligations are those in the LifeSafety Power Standard Terms
and Conditions of Sale for this product, and in no case will LifeSafety Power or its distributors be liable for any incidental, indirect, or
consequential damages arising from the sale, resale, use, or misuse of the product. Specifications are subject to change without notice.
In addition, LifeSafety Power reserves the right to make changes—without notification to Buyer—to processing or materials that do not
aect compliance with any applicable specification.
LifeSafety Power
899 E. Park Avenue
Libertyville, IL 60048 USA
www.lifesafetypower.com
Phone (888) 577-2898
info1@lifesafetypower.com