P03-057
FPV4
4 amp @ 12VDC or
3 amp @ 24VDC
FPV6
6 amp @ 12VDC or 24VDC
FPV102
10 amp @ 12VDC
FPV104
10 amp @ 24VDC
For 230VAC input add "/E" to model number - example FPV6-C8E1/E
For larger enclosure change E1 sux to E2 in model number - example FPV6-C8E2
LifeSafety Power
PH 888.577.2898
TechSupport@LifeSafetyPower.com
Power System
Installation Guide
Smart Power Supply Chargers
Question and Answer IconNeed help?

Do you have a question about the LifeSafety Power FlexPower Vantage FPV4 and is the answer not in the manual?

Summary

Symbol Definitions and Safety Warnings

Warnings

Alerts installers to potential hazards and safety precautions during installation.

FPV4 Power Supply Overview

AC Voltage Select Jumper

Explains the jumper for selecting 120V or 230V AC input.

Voltage Selection Jumper

Details the jumper for selecting 120V or 24V DC output voltage.

FAI and Charge Current Configuration Switches

Details switches for FAI selection and charge current settings.

Main DC Output

Details the main DC output and its configuration options.

FPV6 Power Supply Overview

12;24 V Selection Jumper

Details the jumper for selecting 12V or 24V DC output voltage.

FPV102;104 Power Supply Overview

AC Input Voltage Selection

Explains the jumper for selecting 120V or 230V AC input.

Charge Current; Main output FAI Configuration Switches

Details switches for FAI selection and charge current settings.

Main Output

Details the main DC output and its configuration options.

Battery Terminal Connection

Explains connecting the optional backup battery.

FAI Input Usage

Activation with Normally Open Relay Contact

Explains FAI activation using a Normally Open relay contact.

Latching the FAI Input

Describes how to achieve latching functionality for the FAI input.

Activation with Normally Closed Relay Contact

Explains FAI activation using a Normally Closed relay contact.

FAI Activation with NO Relay and AC Fault Override

Details FAI activation with NO contact and AC Fault override.

Activation with Voltage Input

Explains FAI activation using a voltage input signal.

Tamper Switch Wiring and Installation

FPV4; FPV6 Specifications

FPV102; FPV104 Specifications

General Applications and Compliance

Overview

The LifeSafety Power Vantage Power System is a series of smart power supply chargers designed for various applications, including proprietary burglar alarm and access control systems. The system includes models FPV4, FPV6, FPV102, and FPV104, each offering different output capabilities.

Function Description:

The Vantage Power System provides regulated DC power for security and access control applications. It features an AC input for primary power, with options for 120VAC or 230VAC operation (requiring a jumper cut for 230VAC). The power supplies offer a main DC output, which can be configured for either constant or switched operation based on the Fire Alarm Input (FAI) settings. An auxiliary voltage output is also provided. The system includes a battery terminal connection for optional backup batteries, ensuring continuous operation during power outages. Fault contacts (System Fault and AC Fault) are available for monitoring by a listed control panel, and a DataLink connection allows for optional programming and monitoring via a NetLink network module. The FAI input allows for integration with Fire Alarm Control Panels (FACP) and can be configured to accept Normally Open (NO), Normally Closed (NC), Open Collector, or Voltage inputs.

Important Technical Specifications:

FPV4:

  • AC Input: 120VAC or 230VAC at 50-60Hz, 1.8A maximum current.
  • Standby Current: 80mA.
  • DC Output at 12V Setting: 11.3-12.0V, 4A Max Current, 120mV Ripple & Noise, ±2% Regulation, 82% Efficiency.
  • DC Output at 24V Setting: 23.5-24.0V, 3A Max Current, 240mV Ripple & Noise, ±2% Regulation, 83% Efficiency.
  • Auxiliary Output (12V/24V): 1.5A max.
  • Battery: 4-40AH Lead Acid or Gel Cell, 1A (±10%) maximum charge current (adjustable via DIP switch). Low battery disconnect at 70% of nominal battery voltage.
  • Fuse Rating: ATM 15A.
  • BTU Output: 34-41 BTU/Hr.
  • Fault Setpoints: Low AC at 95V (±6%), Output Voltage at ±10% of nominal.
  • Fault Relay Contacts: AC FLT 1A at 24VDC, SYS FLT 1A at 24VDC.
  • Operating Temperature: 0-49°C.
  • Board Size / Weight: 6.0L x 4.0W x 2.50"H | 1.0 lbs.
  • Enclosure Size / Weight: 14H x 12W x 4.5"D | 14 lbs.

FPV6:

  • AC Input: 120VAC or 230VAC at 50-60Hz, 3.7A maximum current.
  • Standby Current: 150mA.
  • DC Output at 12V Setting: 11.2-12.0V, 6A Max Current, 120mV Ripple & Noise, ±2% Regulation, 88% Efficiency.
  • DC Output at 24V Setting: 23.2-24.0V, 6A Max Current, 240mV Ripple & Noise, ±2% Regulation, 85% Efficiency.
  • Auxiliary Output (12V/24V): 1.5A max.
  • Battery: 4-80AH Lead Acid or Gel Cell, 1.6A (±10%) maximum charge current (adjustable via DIP switch). Low battery disconnect at 70% of nominal battery voltage.
  • Fuse Rating: ATM 15A.
  • BTU Output: 44-62 BTU/Hr.
  • Fault Setpoints: Low AC at 95V (±6%), Output Voltage at ±10% of nominal.
  • Fault Relay Contacts: AC FLT 1A at 24VDC, SYS FLT 1A at 24VDC.
  • Operating Temperature: 0-49°C.
  • Board Size / Weight: 8.25L x 5.50W x 2.50"H | 1.0 lbs.
  • Enclosure Size / Weight: 14H x 12W x 4.5"D | 14 lbs.

FPV102:

  • AC Input: 120VAC or 230VAC at 50-60Hz, 3A maximum current.
  • Standby Current: 110mA.
  • DC Output: 11.3-12.0V, 10A Max Current, 120mV Ripple & Noise, ±2% Regulation, 89% Efficiency.
  • Auxiliary Output: 1.5A max.
  • Battery: 4-80AH Lead Acid or Gel Cell, 1.6A (±10%) maximum charge current. Low battery disconnect at 70% of nominal battery voltage.
  • Fuse Rating: ATM 15A.
  • BTU Output: 55 BTU/Hr.
  • Fault Setpoints: Low AC at 95V (±6%), Output Voltage at ±10% of nominal.
  • Fault Relay Contacts: AC FLT 1A at 24VDC, SYS FLT 1A at 24VDC.
  • Operating Temperature: 0-49°C.
  • Board Size / Weight: 8.25L x 5.50W x 2.50H | 1.0 lbs.
  • Enclosure Size / Weight: 14H x 12W x 4.5"D | 14 lbs.

FPV104:

  • AC Input: 120VAC or 230VAC at 50-60Hz, 5.7A maximum current.
  • Standby Current: 160mA.
  • DC Output: 23.4-25.0V, 10A Max Current, 240mV Ripple & Noise, ±2% Regulation, 91% Efficiency.
  • Auxiliary Output: 1.5A max.
  • Battery: 4-80AH Lead Acid or Gel Cell, 1.6A (±10%) maximum charge current. Low battery disconnect at 70% of nominal battery voltage.
  • Fuse Rating: ATM 15A.
  • BTU Output: 92 BTU/Hr.
  • Fault Setpoints: Low AC at 95V (±6%), Output Voltage at ±10% of nominal.
  • Fault Relay Contacts: AC FLT 1A at 24VDC, SYS FLT 1A at 24VDC.
  • Operating Temperature: 0-49°C.
  • Board Size / Weight: 8.25L x 5.50W x 2.50"H | 1.0 lbs.
  • Enclosure Size / Weight: 14H x 12W x 4.5"D | 14 lbs.

Usage Features:

  • Voltage Selection: FPV4 and FPV6 models allow selection between 12VDC and 24VDC output via a jumper. FPV102 and FPV104 have fixed output voltages (12V/10A and 24V/10A respectively).
  • AC Input Voltage Selection: A jumper must be cut for 230VAC input; leave intact for 120VAC. Failure to do so will damage the system and void the warranty.
  • Fire Alarm Input (FAI): Configurable for various input types (NO, NC, Open Collector, Voltage) and can control the main output (constant or switched). Latching FAI input is also possible.
  • Charge Current Configuration: DIP switches allow adjustment of battery charge current (High or Low).
  • LED Indicators: AC ON (Green) indicates valid AC input; FAI LED (Red) indicates FAI activation; DC ON (Green for 12V, Blue for 24V on FPV6/104) indicates voltage presence on the main output.
  • Fault Monitoring: System Fault and AC Fault contacts provide status to a control panel.
  • Enclosure Mounting: Designed for wall-mount installation, with specific instructions for marking, pre-drilling, and securing the enclosure. For UL1076 applications, two supplied 1" screws must be installed to the cover for additional security.
  • Wire Routing: Class 2 Power Limited wiring must be separated from non-power limited wiring by a minimum of 1/4 inch and use separate knockouts. All wiring through knockouts must be enclosed in rigid or flexible metal conduit.
  • Canadian Installations: Requires an external, readily accessible disconnect device for permanently connected equipment and output circuits not connected to removable terminal strips.
  • Tamper Switch Wiring: A normally closed tamper switch can be integrated for monitoring by a host panel, either directly or in series with the System Fault relay. Required for UL1076 installations.
  • UL Compliance: The power supply must be installed within a protected area and mounted in a Listed LifeSafety Power enclosure. Locking devices must be configured for fail-safe operation upon alarm.

Maintenance Features:

  • Battery Maintenance: Batteries should be maintained at an ambient temperature between 0-49°C (32-120°F). The system and any batteries should be tested at least once per year.
  • Fuse Replacement: Replace fuses only with the same type and rating as indicated in the specifications section.
  • Service: Installation and service should only be performed by qualified service personnel and conform to all local codes. Always confirm the absence of AC power with a meter before servicing.
  • Wiring Integrity: Ensure all wiring is routed and secured to prevent accidental open or short circuit conditions.
  • Output Voltage Verification: Test and verify output voltage before connecting the load.
  • DataLink Connection: Allows for optional programming and monitoring of the power supply via a NetLink network module, simplifying diagnostics and configuration.

LifeSafety Power FlexPower Vantage FPV4 Specifications