EasyManua.ls Logo

Lindab RECTANGULAR Series - Page 17

Default Icon
23 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
Filling
Fill the space between the damper and the wall using Fire Batt
(Weichschott) sealing made from two rock wool panels with mini-
mum thickness of 50 mm and minimum density of 140 kg/m³.
The panels must be covered on both faces of the wall with endo-
thermic varnish type PROMASTOP E PASTE or HILTI CFS-CT (mini-
mum thickness of 1 mm) and with an internal perimeter sealant type
PROMASTOP E PASTE or HILTI CFS-S ACR (minimum thickness of 1
mm).
Fire resistance classication
Hole size “D1 x D2”
[mm]
Damper protrusion from
the wall “E”
[mm]
Wall minimum thickness “S”
[mm]
Sealing
Rigid wall
EI 120 S Installation within rigid vertical wall with Fire Batt (Weichschott) sealing
Wall minimum density 550
kg/m³
EI 120 S
(300 Pa)
(B+800 max) x (H+800
max)
185 100
Rock wool 140 kg/
m³ and endothermic
varnish sealing
Flexible wall
EI 120 S Installation within vertical light wall (plasterboard) with Fire Batt (Weichschott) sealing
Wall rock wool minimum
density 100 kg/m³
EI 120 S
(300 Pa)
(B+800 max) x (H+800
max)
185 100
Rock wool 140 kg/
m³ and endothermic
varnish sealing
EI 120 S Installation within vertical light wall (plasterboard) with Fire Batt (Weichschott) sealing
Wall minimum density 995
kg/m³
EI 120 S
(300 Pa)
(B+800 max) x (H+800
max)
185 100
Rock wool 140 kg/
m³ and endothermic
varnish sealing
B Nominal base of the damper
H Nominal height of the damper
D1 Hole base: see table above
D2 Hole height: see table above
E Damper protrusion from the wall: see table above
1. Rock wool panel 50 mm thick with 140 kg/m³ density.
2. PROMASTOP E PASTE or HILTI CFS-S ACR type sealant
3. PROMASTOP E PASTE or HILTI CFS-CT endothermic varnish
4. Wall indicated in the table
Installation within oor with Fire Batt (Weichschott) sealing
Refer to the section Construction supports characteristics for further
information.
Comply with the minimum distances indicated on section Minimum
distances
Floor opening
A opening must be provided in the oor as indicated in the table
and in the drawing
Damper positioning
Position the damper in the opening so that the side of the closing
mechanism extends as indicated in the table and in the drawing.
Filling
Fill the space between the damper and the oor using Fire Batt
(Weichschott) sealing made from two rock wool panels with mini-
mum thickness of 50 mm and minimum density of 140 kg/m³.
The panels must be covered on both faces of the wall with endo-
thermic varnish type PROMASTOP E PASTE or HILTI CFS-CT (mini-
mum thickness of 1 mm) and with an internal perimeter sealant type
PROMASTOP E PASTE or HILTI CFS-S ACR (minimum thickness of 1
mm).
Fire resistance classication
Hole size “D1 x D2”
[mm]
Damper protrusion from the
oor “E”
[mm]
Floor minimum thickness “S
[mm]
Sealing
EI 120 S Installation within oor and Fire Batt (Weichschott) sealing
Floor minimum density 650 kg/m³
EI 120 S
(300 Pa)
(B+800 max) x (H+800
max)
185 150
Rock wool 140 kg/
m³ and endothermic
varnish sealing
B Nominal base of the damper
H Nominal height of the damper

Related product manuals