INSTALLATION
WH25
LINDAB SAFE
18/50
Gypsum blocks light walls
Gypsum blocks wall can be built with special solid gypsum
blocks with interlocking shaped edges as indicated in the
supplier's instructions and according to the following char-
acteristics:
• minimum thickness 70 or 100 mm according to the type
and resistance class required;
• minimum density 995 kg/m³.
It is generally advisable to rst build the wall and then pro-
vide the opening for the re damper.
Aerated concrete oors
Aerated concrete oors can be built during installation or
with preformed slabs with interlocking shaped edges ac-
cording to the following characteristics:
• minimum thickness 100 or 150 mm according to the
type and resistance class required;
• minimum density 650 kg/m³
Poured concrete oors
Poured concrete oors can be built during installation or
with preformed slabs with interlocking shaped edges ac-
cording to the following characteristics:
• minimum thickness 100 or 150 mm according to the re-
sistance class required;
• minimum density 2200 kg/m³.