Sets the input voltage of the drive.
Always set the input voltage of the drive (not
motor) to this parameter d1-00 (input voltage)
Default:
200V class :200V
400V class :460V
0 ∶ 50 Hz (Constant Torque Characteristic 1)
1 ∶ 60 Hz (Constant Torque Characteristic 2)
2 ∶ 60 Hz (Constant Torque Characteristic 3), 50
Hz base
3 ∶ 72 Hz (Constant Torque Characteristic 4), 60
Hz base
4 ∶ 50 Hz (Derated Torque Characteristic 1)
5 ∶ 50 Hz (Derated Torque Characteristic 2)
6 ∶ 60 Hz (Derated Torque Characteristic 3)
7 ∶ 60 Hz (Derated Torque Characteristic 4)
8 ∶ 50 Hz (High Starting Torque Characteristic 1)
9 ∶ 50 Hz (High Starting Torque Characteristic 2)
A ∶ 60 Hz(High Starting Torque Characteristic 3)
B ∶ 60 Hz(High Starting Torque Characteristic 4)
C ∶ 90 Hz, 60 Hz base
D ∶ 120 Hz, 60 Hz base
E ∶ 180 Hz, 60 Hz base
F ∶ 60Hz (Constant Torque Characteristic)
(Default)
When d1-01 ≦ E, parameters d1-02 to d1-11
can be used to monitor the V/F pattern.
When d1-01 = F, parameters d1-02 to d1-11 can
be used to create a V/F pattern.