Installation & Operation Manual
20
2 General venting
Model Manufacturer Vent Model Vent Type Adapter Number Joint Connector Sidewall Kit*
Retaining Bracket /
Adapter*
751-1001
Centrotherm
Eco Systems
Innoflue
Single-Wall
Flex
ISAAL0606 -- --
IATP0606 /
ISTAGL0606
DuraVent
(M & G)
PolyPro
Single-Wall
Flex
FSA-6PVCM-
6PPS
-- 6PPS-HLK --
1251
Centrotherm
Eco Systems
Innoflue Single-Wall ISAA0808 -- -- --
DuraVent
(M & G)
PolyPro Single-Wall FSA-AU8-8PP -- 8PPS-HSTL --
* These parts are only needed if the sidewall termination assembly is used (see FIG. 4-1C on page 24).
Polypropylene
This product has been approved for use with polypropylene
vent with the manufacturers listed in Table 2F.
All terminations must comply with listed options in this manual
and be a single-wall vent offering.
For support and special connections required, see the
manufacturer's instructions. All vent is to conform to standard
diameter and equivalent length requirements established.
When determining equivalent combustion air and vent length
for polypropylene single-wall piping:
• 1 foot of Duravent 4 inch single-wall pipe is equivalent
to 1.6 feet of piping
Use only the adapters and vent system listed in
Tables 2F and 2G. DO NOT mix vent systems
of different types or manufacturers. Failure
to comply could result in severe personal
injury, death, or substantial property damage.
WARNING
Installations must comply with applicable
national, state, and local codes. For Canadian
installation, polypropylene vent must be listed
as a ULC-S636 approved system.
Installation of a polypropylene vent system
should adhere to the vent manufacturer’s
installation instructions supplied with the
vent system.
Table 2F Polypropylene Vent Pipe and Fittings
WARNING
Insulation should not be used on
polypropylene venting materials. The use
of insulation will cause increased vent wall
temperatures, which could result in vent pipe
failure.
The installer must use a specific vent starter
adapter at the flue collar connection. The
adapter is supplied by the vent manufacturer
to adapt to its vent system. See Table 2F
for approved vent adapters. Discard CPVC
starter piece.
NOTICE
All vent connections MUST be secured by the
vent manufacturer's joint connector (FIG.
2-4).
NOTICE
Figure 2-4 Near Boiler Polypropylene Venting
IMG01149
8" POLYPROPYLENE
PIPE
8" POLYPROPYLENE
ADAPTER
MODEL 1251
IMG01148
6" POLYPROPYLENE
PIPE
6" POLYPROPYLENE
A
DAPTER
MODELS 751 - 1001
NOTICE
NOTICE
Table 2G Approved Polypropylene Terminations
Approved Polypropylene Vent Manufacturers
Make Model
Centrotherm Eco Systems InnoFlue SW/Flex
Duravent (M & G Group) PolyPro Single-Wall / PolyPro Flex