iS7 Ethernet Option Manual
32
Service
Service
Code
Definition
Support
for Class
Support
for Instance
0x0E Get Attribute Single No Yes
0x10 Set Attribute Single No Yes
Control Supervisor Object (Class 0x29, Instance 1)
Attribute
Attribute
ID
Access
Attribute
Name
Range
Definition
3 Get / Set
Forward
Run Cmd.
0 Stop
Operation in normal
direction
(Note1)
1
4 Get / Set
Reverse
Run Cmd.
0 Stop
Operation in reverse
direction
(Note1)
1
5 N/A
Net
Control
-
Can be set up as Inverter
parameter only.
6 Get
Drive
State
0 Vendor specific
1 Startup
2 Not Ready (being reset)
3 Ready (stopping)
4
Enabled (running, except
decelerating to stop)
5
Stopping (decelerating to
stop)
6 Fault Stop
7 Faulted (tripped)
7 Get
Running
Forward
0 Stopping
1
Operating in normal
direction
8 Get
Running
Reverse
0 Stopping
1
Operating in normal
direction