Technical catalog for Susol & Metasol ACB
Technical catalog for Susol & Metasol ACB
D
1. Comparison Table upon Types
N Type
Externals
Current
Relays
L / S / I / G / Thermal
Override / MCR
N type current relay +ZSI
(Protective coordination )
Earth leakage/ Ground Fault
External CT ground fault
Current (R / S / T/ N)
A type optional +
Over/Low voltage
Over/Low frequency
Unbalance relay (Voltage/ Current)
Reverse power relay
3 phase voltage/
Current Rms/ Vector
Power (P, Q, S),
PF (3-phase)
Energy (Positive/ Negative)
Frequency, Demand
Fine adjustment for long / short time delay
/ instantaneous / ground fault
Overload protection relays
DO output (Alarm)
Ground fault is not available when using PTA.
Compliance with
IEC60255-3
Same with A type
Available
AvailableAvailable
Reset button
Note1) S/ P Type are only applicable to Susol Series.
Reset, Menu Up/Down,
Left/Right, Enter
Records 10 faults (Fault/
Current / Date and Time)
Same with N type
Long time delay
Short time delay / Instantaneous/
Ground fault SP(Analogue trip)
RS 485 / MODBUS
Self Power +AC/DC 93 ~
253V DC 24/48V
External power source
are required for comm.
Self Power
(Power source works
over 20% of load current.)
Same with N type
256 records
256 records for changes of device
status (Content, Status, Date)
Same with A type
Same with A type Under Self-
Power, current relay only operates
External power source
required for optional relays
and measurement function
A type function +Thermal
(Linear Hot Start)
Same with P type
Same with P type
Same with P type
Same with P type
Same with P type
Same with A type
Same with P type
P type function +The latest
fault waveform(3phases)
Same with A type
Same with A type
Available
Same with N type
P type function +
Harmonics 63
rd
-
3 phase voltage/ current
3 phase waveforms
THD, TDD, K-Factor
Optional
Relays
Measurement
Function
Fine
Adjustment
IDMTL
Relay
Comm.
Timer
Power
Supply
LED
for Trip
Info.
Fault
Record
Event
Record
Operating
Button
Pre Trip
Alarm
A Type
P Type
D
Note 1) Note 1)
S Type